Check code Check code name<br />

Cause<br />

[H16] / [d7] (AI-NET)<br />

Oil level detection circuit error<br />

TK2 temperature detective circuit<br />

error<br />

(Sub-code: 02)<br />

1. Coming-off of TK2 sensor, miswiring, characteristics<br />

error of resistance value<br />

2. Oil-equalization circuit error (Check valve, capillary<br />

clogging, strainer clogging)<br />

3. Refrigerant stagnation in the compressor shell<br />

Is not TK2 sensor<br />

detached?<br />

Yes<br />

Correct installation of<br />

sensor.<br />

No<br />

Is there<br />

no miswiring or<br />

misinstallation on<br />

TK1/TK2/TK3/TK4/TK5<br />

sensors?<br />

No<br />

Yes<br />

Correct miswiring/misinstallation.<br />

TK1: CN531, black<br />

TK2: CN532, green<br />

TK3: CN533, pink<br />

TK4: CN534, yellow<br />

TK5: CN535, red<br />

After resetting<br />

the power<br />

Are<br />

characteristics of TK2<br />

sensor resistance<br />

value normal?<br />

Yes<br />

Start a test operation in COOL or HEAT mode.<br />

Display TK2 sensor temperature on 7-segment display with<br />

SW01/02/03=[1] [13] [2].<br />

No<br />

*See “Outdoor unit temperature sensor<br />

characteristics” on “8-9. Sensor Characteristics”.<br />

Check TK2 sensor temp approx. 10 minutes after compressor 1 has operated.<br />

If low temperature continues (approximately outside temp) or temperature has<br />

little change, a clogging of strainer of oil-equalization circuit, clogging of<br />

capillary tube, or malfunction of check valve is considered.<br />

↓<br />

↓<br />

Error<br />

Strainer<br />

Capillary<br />

Compressor<br />

Sensor error<br />

Replace clogging part.<br />

No error<br />

TK2<br />

Check the clogging<br />

of SV3E valve.<br />

(Note 1)<br />

Error<br />

(Note 1) Refer to the article of the check code [H07].<br />

Replace SV3E valve.<br />

No error<br />

Check I/F P.C. board<br />

Check code Check code name<br />

Cause<br />

[H15] / [A1]<br />

(AI-NET)<br />

Outdoor discharge temperature<br />

sensor (TD2) misconnection<br />

1. Coming-off of TD2 sensor<br />

2. Misinstallation of TD1, TD2, or TD3 sensor,<br />

miswiring, characteristics error of resistance value<br />

Is TD2 sensor<br />

installed correctly?<br />

No<br />

Correct installation of sensor.<br />

Yes<br />

Is there no<br />

miswiring or<br />

misinstallation on<br />

TD1/TD2/ TD3<br />

sensors?<br />

Yes<br />

Correct miswiring/misinstallation.<br />

TD1: CN502, white<br />

TD2: CN503, pink<br />

TD3: CN504, blue<br />

No<br />

Are resistance<br />

characteristics of TD2<br />

sensor normal?<br />

No<br />

Sensor error ➝ Replace the sensor.<br />

Yes<br />

Check I/F P.C. board.<br />

2<br />