Check code Check code name<br />

Cause<br />

[P12] / [11]<br />

(AI-NET)<br />

Indoor fan motor error 1. Wiring error of fan motor connector<br />

2. Fan motor error<br />

3. Indoor P.C. board error<br />

Turn off power supply.<br />

* Detectable in model equipped with DC fan motor<br />

(4-way cassette, 2-way cassette, 1-way cassette,<br />

concealed duct, wall and ceiling types)<br />

Is there<br />

connection error or<br />

disconnection on connector<br />

CN333, CN334 of indoor P.C.<br />

board (MCC-1402)?<br />

Yes<br />

Correct connector connection.<br />

No<br />

Remove connectors CN333 and CN334<br />

on indoor P.C. board (MCC-1402).<br />

Does fan turn<br />

without trouble when<br />

turning it with<br />

hands?<br />

No<br />

Replace indoor fan motor.<br />

Yes<br />

Is<br />

resistance value<br />

between each phase at<br />

motor side of fan motor connector<br />

CN333 on indoor P.C.<br />

board (MCC-1402)<br />

correct? *1<br />

Yes<br />

Is resistance<br />

value at motor side of fan<br />

motor connector CN334 on<br />

indoor P.C. board (MCC-<br />

1402) correct? *2<br />

Yes<br />

No<br />

*1<br />

• Is not winding 1 (Red lead) to 3 (White lead), 3 (White lead) to 5 (Black lead), 5 (Black<br />

lead) to 1 (Red lead) opened/shorted? ➝ Resistance value should satisfy the follows.<br />

[4-way Cassette type]<br />

AP007 to AP030: Approx. 70 to 100Ω<br />

AP036 to AP056: Approx. 35 to 50Ω<br />

[2-way Cassette type]<br />

AP007 to AP015: Approx. 70 to 100Ω<br />

AP018 to AP030: Approx. 30 to 70Ω<br />

AP036 to AP056: Approx. 20 to 50Ω<br />

[1-way Cassette type]<br />

Approx. 30 to 70Ω<br />

[Ceiling type]<br />

AP015 to AP027: Approx. 30 to 70Ω<br />

AP036 to AP056: Approx. 20 to 50Ω<br />

[Wall and concealed duct types]<br />

Approx. 15 to 35Ω<br />

• Is not grounded between cabinet and 1, 3, 5? ➝ Should be 10MΩ or more.<br />

No<br />

*2<br />

Check resistance value of fan motor position detective circuit.<br />

• Is not winding 1 (Yellow lead) to 4 (Pink lead)<br />

opened/shorted? ➝ Resistance should be 5 to 20kΩ.<br />

Replace indoor fan motor.<br />

Replace indoor fan motor.<br />

Is output<br />

of indoor fan motor<br />

position detective signal<br />

correct? *3<br />

Yes<br />

No<br />

*3<br />

Check fan motor position detective signal.<br />

• Measure voltage with tester between 1 and 5 of CN334 on<br />

indoor P.C. board (MCC-1402) under condition of CN333<br />

and CN334 installed and power-ON. ➝ Turn fan slowly with<br />

hands so that pin voltage fluctuates between 0 and 5V.<br />

• Between 4 and 5: 5V<br />

Replace indoor fan motor.<br />

Check indoor P.C. board<br />

(MCC-1402).<br />

Failure ➝ Replace<br />

CN333<br />

CN334<br />

Check code Check code name<br />

Cause<br />

[P10] / [0b]<br />

(AI-NET)<br />

Water overflow in an indoor unit 1. Float SW malfunction<br />

2. Drain pump malfunction<br />

3. Clogging of drain pipe<br />

4. Indoor P.C. board error<br />

Sub-code: Overflowing indoor unit's address<br />

Is float SW<br />

connector (Indoor<br />

control P.C. board<br />

CN34) connected<br />

normally?<br />

No<br />

Correct connector connection.<br />

Yes<br />

Does float SW<br />

operate?<br />

No<br />

Yes<br />

No<br />

Is wiring normal?<br />

Check and correct wiring.<br />

Yes<br />

Check indoor P.C. board.<br />

Failure ➝ Replace<br />

Does drain pump<br />

operate?<br />

No<br />

Yes<br />

Is power supply to<br />

drain pump normal?*<br />

No<br />

Check indoor P.C. board.<br />

Failure ➝ Replace<br />

Yes<br />

Check drain pipe, etc. Replace drain pump, and check cabling.<br />

* Check there is 220-240V voltage of 1-3 pin of CN68 on indoor P.C. board.<br />

218