Check code Check code name<br />

Cause<br />

[P15] / [AE]<br />

(AI-NET)<br />

Gas leak detection<br />

TS condition (Sub-code: 01)<br />

1. Outdoor unit service valve closed<br />

2. Outdoor PMV error<br />

3. TS1 sensor error<br />

4. Refrigerant shortage, clogging refrigerant circuit<br />

5. 4-way valve error<br />

6. SV4 circuit error<br />

Are service valves<br />

at gas and liquid<br />

side fully opened?<br />

No<br />

Open service valves fully.<br />

Yes<br />

Is outdoor PMV normal?<br />

1. Connector connection<br />

2. Wiring<br />

3. Coil<br />

4. Valve body<br />

5. Outdoor I/F P.C. board<br />

No<br />

Connectors: PMV1: CN300,<br />

PMV2: CN301, PMV4: CN303<br />

Repair outdoor PMV.<br />

Yes<br />

Are<br />

characteristics<br />

of TS1 sensor<br />

resistance<br />

normal?<br />

Yes<br />

No<br />

* See “Outdoor unit temperature sensor<br />

characteristics” on “8-9. Sensor Characteristics”.<br />

Replace TS1 sensor.<br />

Does discharge<br />

refrigerant gas bypass<br />

to suction side through<br />

4-way valve?<br />

Yes<br />

Check and replace 4-way<br />

valve and coil.<br />

No<br />

Is there any<br />

leakage on SV41,<br />

42 and 43 valve<br />

circuits?<br />

Yes<br />

No<br />

Repair SV41/SV42/SV43<br />

valve circuits.<br />

(Coil, valve body, disconnection<br />

of wire, etc.)<br />

Refrigerant shortage,<br />

clogging, pipe breakage.<br />

(Check there is no clogging and pipe<br />

breakage, and then recharge refrigerant.)<br />

Check code Check code name<br />

Cause<br />

[P13] / [47]<br />

(AI-NET)<br />

Outdoor liquid back detection<br />

error<br />

1. PMV1/PMV2 error<br />

2. Pd sensor, Ps sensor error<br />

3. Clogging of SV2 circuit<br />

4. Clogging of SV3B circuit and/or balance pipe<br />

5. Leakage at a check valve on a main discharge pipe<br />

6. Outdoor I/F P.C. board error<br />

Are<br />

connections of outdoor<br />

PMV1/PMV2/PMV4<br />

connectors correct?<br />

No<br />

Correct connector connection.<br />

(PMV1: CN300, PMV2:<br />

CN301, PMV4: CN303)<br />

Yes<br />

Are<br />

operations of outdoor<br />

PMV1/PMV2/PMV4<br />

normal?<br />

No<br />

PMV error<br />

Yes<br />

Are<br />

characteristics of<br />

Pd sensor/Ps sensor<br />

output voltage<br />

normal?<br />

No<br />

Pd sensor/Ps sensor error<br />

Yes<br />

Is SV2 valve coil<br />

correctly connected?<br />

No<br />

Correct connector connection.<br />

(CV2: CN302)<br />

Yes<br />

Are balance pipe<br />

service valves of<br />

all units fully<br />

opened?<br />

No<br />

Open fully balance pipe<br />

service valves of all units.<br />

Yes<br />

Is there no<br />

clogging of SV3B<br />

valve?<br />

Yes<br />

Replace clogging parts.<br />

No<br />

Is there no<br />

clogging of SV3B valve<br />

of any other unit than<br />

malfunctioning one?<br />

Yes<br />

Replace clogging parts.<br />

No<br />

Is there no leakage of<br />

check valve of main<br />

discharge pipe in follower<br />

units in which compressors<br />

are driven in cooling<br />

operation?<br />

Yes<br />

Replace check valve of main<br />

discharge pipe.<br />

Yes<br />

Check I/F P.C. board.<br />

219