• Check the additional amount of refrigerant.<br />

Checklist 2<br />

Calculate the additional amount of refrigerant from the additional amount of refrigerant (A) by the pipe diameter on<br />

the liquid side, the pipe length to be connected, and the corrective amount of refrigerant (C) according to system<br />

horsepower.<br />

Additional amount<br />

of refrigerant<br />

=<br />

Actual liquid pipe length × Additional amount<br />

of refrigerant per 1 m of liquid pipe<br />

+<br />

Corrective amount of refrigerant<br />

according to system horsepower<br />

First, enter the total length for each liquid pipe diameter in the following table, and then calculate the additional<br />

amount of refrigerant by pipe length.<br />

<br />

Pipe diameter on the liquid<br />

side<br />

Standard amount of<br />

refrigerant<br />

kg/m<br />

Total pipe length on each liquid side<br />

m<br />

Next, refer to the following table for the corrective amount of refrigerant (C) according to system horsepower.<br />

<br />

Lastly, add the additional amount of refrigerant by pipe length (A) to the corrective amount of refrigerant by<br />

combined horsepower (C). This is the final additional amount of refrigerant.<br />

If a minus sign is indicated as the result, do not add the refrigerant (= 0 kg).<br />

<br />

122<br />

Additional amount of refrigerant pipe diameter on<br />

each liquid side<br />

kg<br />

Ø6.4 0.025 × = kg<br />

Ø9.5 0.055 × = kg<br />

Ø12.7 0.105 × = kg<br />

Ø15.9 0.160 × = kg<br />

Ø19.0 0.250 × = kg<br />

Ø22.2 0.350 × = kg<br />

Additional amount of refrigerant by pipe length (A) kg<br />

Standard type<br />

High Efficiency type<br />

Combined HP (HP) Combined outdoor units (HP) C (Corrective amount of refrigerant) (kg)<br />

8 8HP – – – 1.5<br />

10 10HP – – – 2.5<br />

12 12HP – – – 3.5<br />

14 14HP – – – 8.5<br />

16 16HP – – – 10.5<br />

18 10HP 8HP – – 0.0<br />

20 10HP 10HP – – 3.0<br />

22 12HP 10HP – – 5.0<br />

24 12HP 12HP – – 7.5<br />

26 16HP 10HP – – 8.5<br />

28 16HP 12HP – – 9.5<br />

30 16HP 14HP – – 11.5<br />

32 16HP 16HP – – 12.5<br />

34 12HP 12HP 10HP – 3.0<br />

36 12HP 12HP 12HP – 4.0<br />

38 16HP 12HP 10HP – 6.0<br />

40 16HP 12HP 12HP – 7.0<br />

42 16HP 14HP 12HP – 8.0<br />

44 16HP 16HP 12HP – 10.0<br />

46 16HP 16HP 14HP – 12.0<br />

48 16HP 16HP 16HP – 14.0<br />

16 8HP 8HP – – 0.0<br />

24 8HP 8HP 8HP – -4.0<br />

26 10HP 8HP 8HP – -4.0<br />

28 10HP 10HP 8HP – -2.0<br />

30 10HP 10HP 10HP – 0.0<br />

32 8HP 8HP 8HP 8HP -6.0<br />

34 10HP 8HP 8HP 8HP -6.0<br />

36 10HP 10HP 8HP 8HP -6.0<br />

38 10HP 10HP 10HP 8HP -6.0<br />

40 10HP 10HP 10HP 10HP -5.0<br />

42 12HP 10HP 10HP 10HP -4.0<br />

44 12HP 12HP 10HP 10HP -2.0<br />

46 12HP 12HP 12HP 10HP 0.0<br />

48 12HP 12HP 12HP 12HP 2.0<br />

Additional amount of refrigerant by pipe length (A) kg<br />

Corrective amount of refrigerant according to combined horsepower (C) kg<br />

Additional amount of refrigerant kg<br />

(A)<br />

(C)