NO. Item Specification outline Remarks<br />

6<br />

Cold air<br />

discharge<br />

prevention<br />

control<br />

1. In heating operation, the upper limit of the fan tap is set according to the lower of<br />

whichever is the higher between TC2 sensor and TCJ sensor temperatures, on<br />

the one hand, and TC1 sensor temperature, on the other.<br />

• If the fan continuously operates in zone B for 6 minutes, it automatically moves<br />

into zone C.<br />

• During defrosting, the control point is shifted by +6°C.<br />

(°C)<br />

32<br />

30<br />

28<br />

26<br />

20<br />

16<br />

D<br />

C<br />

A<br />

E<br />

B<br />

Zone A:OFF<br />

Zone B:26 °C or above and<br />

below 28 °C<br />

Breeze<br />

Zone C:28 °C or above and<br />

below 30 °C<br />

Low<br />

Zone D:30 °C or above and<br />

below 32 °C<br />

Medium<br />

Zone E:High<br />

TCJ: Indoor heat<br />

exchanger sensor<br />

temperature<br />

• In zones D and E,<br />

priority is given to the<br />

remote controller fan<br />

speed setting.<br />

• In zone A, “HEATING<br />

STANDBY ” is<br />

displayed.<br />

Freeze<br />

prevention<br />

control (low<br />

temp. release)<br />

1. During cooling, the air conditioner is operated in the manner described below<br />

according to the temperature readings of the TC1, TC2 and TCJ sensors.<br />

• If zone J operation is detected for 5 minutes, the air conditioner is forced into<br />

thermo OFF.<br />

• In zone K, the timer is put on pause, with the current timer count retained.<br />

• If zone I operation is detected, the timer count is cleared, and the air conditioner<br />

returns to normal operation.<br />

• If continuous zone J operation forces the air conditioner into thermo OFF, the<br />

indoor fan is operated in breeze mode until it moves into zone I.<br />

The control is terminated under the following conditions:<br />

Termination conditions<br />

1)TC1 12°C, TC2 12°C, and TCJ 12°C<br />

2)Passage of 20 minutes after stoppage<br />

TC1: Indoor heat<br />

exchanger sensor<br />

temperature<br />

7<br />

P1<br />

(°C)<br />

Q1<br />

J<br />

I<br />

K<br />

a<br />

TC1 TC2, TCJ<br />

P1 10°C(5°C) -10°C<br />

Q1 0°C -14°C<br />

Temperature in ( ): If the temperature is below<br />

this value when the power is turned on, the air<br />

conditioner is forced into thermo OFF.<br />

2. During cooling, the air conditioner is operated in the manner described below<br />

according to the temperature readings of the TC2 and TCJ sensors.<br />

• If zone M operation is detected for 45 minutes, the air conditioner is forced into<br />

thermo OFF.<br />

• In zone N, the timer is put on pause, with the current timer count retained.<br />

• When the air conditioner goes back into zone M, timer count is resumed from<br />

the retained value.<br />

• If zone L operation is detected, the timer count is cleared, and the air conditioner<br />

returns to normal operation.<br />

(°C)<br />

P2<br />

Q2<br />

L<br />

N<br />

M<br />

TC2, TCJ<br />

P2 5<br />

Q2 -2.0<br />

Reset conditions<br />

1)TC1 12°C, TC2 12°C and TCJ 12°C<br />

2)Passage of 20 minutes after stoppage<br />

* With models without<br />

TC2, TC2 is not part<br />

of the control<br />

parameters.<br />

72