6-6. Applied Control of Indoor Unit<br />

Control system using remote control interface (TCB-IFCB4E2)<br />

Wiring and setting<br />

• In the case of group control, the control system functions as long as it is connected to one of the indoor units<br />

(control P.C. board) in the group. If it is desired to access the operation and error statuses of other units, relevant<br />

signals must be brought to it from those units individually.<br />

▼ Control items<br />

(1) Start/Stop input signal Start/stop of unit<br />

(2) In-operation signal Output present while unit in normal operation<br />

(3) Error signal Output present while alarm (e.g. serial communication error or operation of protective<br />

device for indoor/outdoor unit) being activated<br />

▼ Wiring diagram of control system using remote control interface (TCB-IFCB4E2)<br />

Input IFCB4E2: No-voltage ON/OFF serial signal<br />

Output No-voltage contact (in-operation and error indication)<br />

Contact capacity: Max. AC 240V, 0.5A<br />

Indoor control P.C. board<br />

Start/stop input<br />

COM (GND)<br />

Remote controller disabling/enabling input<br />

In-operation signal output<br />

COM (+12V)<br />

Error signal output<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

CN61<br />

T10<br />

(yellow)<br />

1<br />

2<br />

3<br />

4<br />

CN06<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

CN13<br />

ON side<br />

Start signal input<br />

OFF side<br />

Stop signal input<br />

COM<br />

In-operation signal output<br />

Error signal output<br />

Power source 220-240V<br />

TCB-IFCB4E2<br />

103