Check code Check code name<br />

Cause<br />

[P26] / [14]<br />

(AI-NET)<br />

G-Tr short-circuit protection error 1. Outdoor unit power error<br />

2. IPDU error/Wire connection error<br />

3. Compressor error<br />

4. IPDU P.C. board error<br />

Sub-code:<br />

01: Compressor 1, 02: Compressor 2, 03: Compressor 3<br />

Is power voltage<br />

of outdoor unit<br />

normal?<br />

No<br />

Correct power line.<br />

Yes<br />

Is wire connector<br />

connection on<br />

INV P.C. board<br />

normal?<br />

No<br />

Correct connection of wire<br />

connector.<br />

Yes<br />

Is there no fusing<br />

of AC30A fuse?<br />

No<br />

Replace fuse and A3-IPDU<br />

P.C. board.<br />

Yes<br />

Is compressor<br />

normal?<br />

No<br />

Replace compressor.<br />

Yes<br />

Is smoothing<br />

condenser normal?<br />

(1500µF, 400V)<br />

No<br />

Check capacity comingout/external<br />

appearance.<br />

Yes<br />

Replace A3-IPDU P.C. board.<br />

Check code Check code name<br />

Cause<br />

[P22] / [1A]<br />

(AI-NET)<br />

Outdoor fan IPDU error 1. Fan lock<br />

2. Fan IPDU P.C. board error<br />

3. Overload<br />

4. External cause such as blast<br />

Sub-code:<br />

0∗: IGBT short circuit<br />

1∗: Position detection circuit error<br />

3∗: Motor lock<br />

4∗: Motor current error detected<br />

C∗: TH sensor temperature error<br />

D∗: TH sensor error<br />

E∗: Fan Vdc error<br />

Ignore the indication (0-F) on "∗" digit.<br />

Is wire<br />

connector connection<br />

on fan IPDU P.C. board<br />

normal?<br />

No<br />

Correct wire connector<br />

connection.<br />

Yes<br />

Is not outdoor fan<br />

motor locked?<br />

Yes<br />

No<br />

Is the resistance of<br />

the motor's winding<br />

wire normal?<br />

No<br />

* Resistance of the winding: 1.1-1.7Ω (between R-S, R-T and S-T)<br />

Replace motor.<br />

Yes<br />

Is sub-code of<br />

outdoor I/F P.C.<br />

board [0*]?<br />

Yes<br />

Replace fan IPDU.<br />

No<br />

Is there<br />

no problem such as<br />

stuffing or blast blowing<br />

to discharge port of<br />

outdoor fan?<br />

Yes<br />

Clear the cause of overload.<br />

No<br />

Check fan IPDU.<br />