Item Description of operation, numerical data, and other information Remarks<br />

4. Oil level<br />

detection<br />

control<br />

1)Judgment as to whether an optimum amount of oil is present in the compressor<br />

cases is made on the basis of the temperature readings of sensors TK1 to TK5.<br />

This control function is performed by the header unit and each follower unit<br />

individually.<br />

2)In concrete terms, judgment is based on the relationship between the temperature<br />

measurements provided by TK1, TK2 or TK3, on the one hand, and those provided<br />

by TK4 or TK5, on the other. If there is depletion, oil equalization control takes over.<br />

3)This control function is performed whenever at least one compressor is in<br />

operation.<br />

(SV3D)<br />

SV<br />

Oil separator<br />

SV<br />

(SV2)<br />

• Oil level detection takes<br />

place regardless of the<br />

number of compressors,<br />

whether it be one, two or<br />

three.<br />

• Rough guide for oil level<br />

judgment<br />

1) If TK1 - TK4 14 °C,<br />

oil level of compressor 1<br />

is optimum.<br />

2) If TK2 - TK4 14 °C,<br />

oil level of compressor 2<br />

is optimum.<br />

3) If TK3 - TK4 14 °C,<br />

oil level of compressor 3<br />

is optimum.<br />

OFF<br />

OFF<br />

(SV41)<br />

SV<br />

(TD1)<br />

OFF<br />

High (SV3C)<br />

pressure<br />

SW<br />

SV<br />

High<br />

pressure<br />

SW<br />

SV<br />

(TD2)<br />

(SV42)<br />

OFF<br />

High<br />

pressure<br />

SW<br />

SV<br />

(SV43)<br />

(TD3)<br />

OFF<br />

Compressor<br />

1<br />

(inverter)<br />

(TK4)<br />

Compressor<br />

2<br />

(inverter)<br />

Compressor<br />

3<br />

(inverter)<br />

(TK1)<br />

(TK2)<br />

(TK3)<br />

SV<br />

ON<br />

(TK5) Oil header<br />

(SV3E)<br />

SV<br />

(SV3F)<br />

ON<br />

(SV3A)<br />

OFF<br />

Check valve<br />

SV<br />

SV<br />

OFF<br />

(SV3B)<br />

Check valve<br />

Balance pipe<br />

Packed valve<br />