(3) Batch start/stop (ON/OFF) function<br />

This function is provided to start/stop collectively all the indoor units connected to the same system by using<br />

switches on the interface board of the header unit.<br />

<br />

0<br />

Power ON<br />

Be sure to turn on power at the indoor side<br />

before power-ON of outdoor unit.<br />

If an error is already displayed with SW01/SW02/SW03<br />

being [1/1/1], return the status to normal one according<br />

to troubleshooting and then execute a test operation.<br />

Set up the operation mode of the remote controller.<br />

(If it is not set up, the operation continues with the current mode.)<br />

(FAN/COOL/HEAT)<br />

The unit which is not given with priority by heating<br />

priority control, cooling priority control, and selection<br />

of cooling or heating mode is not operated.<br />

In this case, " operation ready" or " operation<br />

mode controlled" is displayed on the remote controller.<br />

Set SW01/SW02/SW03 on the interface P.C. board of the header unit<br />

to [2/7/1].<br />

([C.H ] is displayed on 7-segment display [A].)<br />

Press SW04 on the same board for 2 seconds or more.<br />

Start<br />

The indoor unit to be started operates.<br />

Operation check<br />

If the discharge temperature does not change<br />

though COOL or HEAT has been set up from the<br />

remote controller, misconnection is considered.<br />

Press the push-switch SW05 on the interface P.C. board of the<br />

header unit for 2 seconds or more.<br />

Stop<br />

After test operation, return the rotary switches SW01/SW02/SW03 on<br />

the interface P.C. board of the header unit to [1/1/1].<br />

End<br />

7-segment display [A]<br />

SW04<br />

7-segment display [B]<br />

SW05<br />

SW01 SW02 SW03<br />

<br />