Note 1: Criteria for the difference between suction and discharge temperatures<br />

(1) Cooling operation<br />

After operating for a minimum of 30 minutes in “COOL” mode, if the T dry bulb temperature difference between<br />

suction and discharge air of the indoor unit is 8°C or more, it is normal.<br />

(2) Heating operation<br />

After operating for a minimum of 30 minutes in “HEAT” mode, if the T dry bulb temperature difference between<br />

suction and discharge air of the indoor unit is 15°C or more, it is normal.<br />

* If demand from the indoor unit on the outdoor unit is low because the difference between the temperature set<br />

by the remote controller and the temperature of the room is small, then the T temperature difference is small.<br />

* Consider that T temperature difference may diminish in cases of a system in which the connected indoor unit<br />

capacity exceeds the outdoor unit capacity, the pipe length is long, or a large difference exists among outdoor<br />

units.<br />

Note 2: Criteria for operating power current<br />

The table below shows the maximum current for each outdoor unit. Under standard conditions, operating current<br />

is about 80% of the value shown in the table below.<br />

Outdoor unit MMY-MAP 0804 1004 1204 1404 1604<br />

Current value (A) 23.5 25.5 28.5 33.2 36.5<br />

Note 3: Criteria for cycle status<br />

(1) These data are based on operating a 4-way Air Discharge Cassette type air conditioner of 100% connection<br />

with standard piping length.<br />

Data may vary depending on temperature conditions, installed pipe length, and room shape combinations, or<br />

indoor unit connection capacity.<br />

For pressure criteria in different temperature conditions, refer to (2).<br />

Outdoor<br />

unit<br />

MMY-<br />

MAP<br />

0804<br />

1004<br />

1204<br />

1404<br />

Operating<br />

mode<br />

Pressure<br />

(MPa)<br />

Pd<br />

Cooling 3.1 0.8 90 15 10 40 40 65 65 65 High 27/19 35/-<br />

1604<br />

Heating 3.1 0.7 90 2 35 2 30 65 65 65 High 20/- 7/6<br />

* This compressor is driven with a 4-pole motor. The value of the compressor frequency (rps) measured with a clamp meter at the compressor<br />

lead line is two times the rotation count (rps) of the compressor.<br />

* Each compressor may have a different frequency as a measure against resonance.<br />

* The temperature of the indoor heat exchanger (TC) indicates TCJ sensor temperature when cooling, and TC2 sensor temperature when<br />

heating, respectively.<br />

(2) Criteria for operating pressure<br />

Ps<br />

Discharge<br />

(TD)<br />

Suction (TS)<br />

Pipe surface temperature<br />

(°C)<br />

Indoor heat<br />

exchanger<br />

(TC)<br />

Outdoor heat<br />

exchanger<br />

(TE)<br />

High pressure (MPa) 2.0~3.3 2.5~3.3<br />

Pressure<br />

Low pressure (MPa) 0.5~0.9 0.5~0.7<br />

* Criteria after 15 minutes or more has passed since operating started<br />

Liquid<br />

temperature<br />

(TL)<br />

Number of compressor rotations<br />

(rps)*<br />

Compressor Compressor Compressor<br />

1 2 3<br />

(3) On rotations of outdoor fans<br />

Outdoor fans may rotate slowly to control pressure when cooling with low outer air temperature or heating with<br />

excessive load. For control content, also refer to items in Section 5, “Control Outline: Outdoor Unit, Outdoor Fan<br />

Control.”<br />

Indoor<br />

fan<br />

Air temperature<br />

condition<br />

(DB/WB) (°C)<br />

Cooling 2.9 0.9 85 15 10 40 40 50 50 – High 27/19 35/-<br />

Heating 3.0 0.7 85 5 35 3 30 50 50 – High 20/- 7/6<br />

Cooling 3.0 0.8 85 15 8 40 40 65 65 – High 27/19 35/-<br />

Heating 3.1 0.7 85 4 35 2 30 65 65 – High 20/- 7/6<br />

Cooling 3.1 0.8 85 17 8 40 40 70 70 – High 27/19 35/-<br />

Heating 3.1 0.7 90 2 35 2 30 75 75 – High 20/- 7/6<br />

Cooling 3.0 0.8 85 15 10 40 40 60 60 60 High 27/19 35/-<br />

Heating 3.1 0.7 85 4 35 3 30 60 60 60 High 20/- 7/6<br />

Operating mode Cooling Heating<br />

Indoor temperature (°C) 18~32 15~32<br />

Outdoor temperature (°C) 25~35 5~35<br />

Indoor<br />

Outdoor<br />

147