3 Push the button.<br />

• The address of one of the indoor units connected to the selected refrigerant line is indicated on the LCD<br />

display and the fan and louvers of the unit are activated.<br />

At first, the current indoor unit address is displayed in SET DATA.<br />

(No system address is indicated.)<br />

CODE No.<br />

SET DATA<br />

SETTING<br />

UNIT No.<br />

R.C.<br />

No.<br />

TEMP.<br />

ON / OFF<br />

4<br />

8<br />

Finish<br />

FILTER<br />

RESET TEST<br />

TIMER SET<br />

TIME<br />

SET CL<br />

5, 7<br />

Press to finish<br />

setting.<br />

6<br />

4 Push the TIME / buttons repeatedly to change the value of the indoor unit address in SET<br />

DATA.<br />

Change the value in SET DATA to that of a new address.<br />

5 Push the button to confirm the new address on SET DATA.<br />

6<br />

UNIT LOUVER<br />

Push the button (left side of the button) repeatedly to select another address to change.<br />

Each time you push the button, the indoor unit numbers in a refrigerant line are indicated one<br />

after another. Only the fan and louvers of the selected indoor unit are activated.<br />

Repeat steps 4 to 6 to change the indoor unit addresses so as to make each of them unique.<br />

7 Push the button.<br />

(All the segments on the LCD display light up.)<br />

8 Push the button to finish the procedure.<br />

Resetting the address<br />

(Resetting to the factory default (address undecided))<br />

Method 1<br />

Clearing each address separately using a wired remote controller.<br />

Set the system address, indoor unit address and group address to “0099” using a wired remote controller.<br />

(For the setting procedure, refer to the address setting procedures using the wired remote controller on the<br />

previous pages.)<br />

Method 2<br />

Clearing all the indoor unit addresses on a refrigerate line at once from the outdoor unit.<br />

1 Turn off the refrigerant line to reset to the factory default and set the header outdoor unit of the<br />

line as below.<br />

1) Disconnect the relay connectors between the [U1, U2] and [U3, U4] terminals.<br />

(Leave them as they are if they have already been disconnected.)<br />

135