16.04.2015 Views

MULTI TYPE

MULTI TYPE

MULTI TYPE

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

6-3. Optional Connector Specifications of Indoor P.C.<br />

Board<br />

Function Connector No. Pin No.<br />

Fan output CN32<br />

1<br />

2<br />

HA<br />

CN61<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

Optional output CN60<br />

1<br />

2<br />

3<br />

4<br />

5<br />

6<br />

External CN80<br />

1<br />

error input<br />

2<br />

3<br />

FILTER<br />

Optional error<br />

CHK<br />

Operation check<br />

DISP<br />

Display mode<br />

EXCT<br />

Demand<br />

CN70<br />

CN71<br />

CN72<br />

CN73<br />

1<br />

2<br />

1<br />

2<br />

1<br />

2<br />

1<br />

2<br />

DC12V<br />

Output<br />

Start/stop input<br />

0V(COM)<br />

Remote controller disabling input<br />

In-operation output<br />

DC12V(COM)<br />

Alarm output<br />

DC12V(COM)<br />

Defrosting output<br />

Thermostat ON output<br />

Cooling output<br />

Heating output<br />

Fan output<br />

DC12V(COM)<br />

DC12V(COM)<br />

External error input<br />

0V<br />

Check mode input<br />

0V<br />

Display mode input<br />

0V<br />

Demand input<br />

0V<br />

Specification Remarks<br />

"FILTER/optional/humidifier<br />

setting" input<br />

Factory default setting: ON when indoor unit in operation and OFF when indoor unit at rest<br />

* Fan can be operated on its own by pressing FAN button on remote controller (DN = 31)<br />

Start/stop input for HA (J01: In place/Removed = Pulse input (factory default)/Step input)<br />

Enables/disables start/stop control via remote controller<br />

ON during operation (HA answerback signal)<br />

ON while alarm ON<br />

ON while outdoor unit defrosted<br />

ON while real thermostat ON (compressor ON)<br />

ON while air conditioner in cooling or related operation (COOL, DRY or cooling under AUTO mode)<br />

ON while air conditioner in heating operation (HEAT or heating under AUTO mode)<br />

ON while indoor fan ON (air cleaner in use or via interlock wiring)<br />

Generates test code L30 and automatically shuts down air conditioner (only if condition persists<br />

for 1 minute)<br />

Factory default setting to be humidifier (evaporative + drain pump OFF)<br />

Used for control of optional error input (display of action of protective device for equipment connected externally)<br />

* "Optional error input" setting to be performed via the remote controller (DN = 24)<br />

Used for indoor operation check (prescribed operational status output, such as indoor fan "H" or<br />

drain pump ON, to be generated without communication with outdoor unit or remote controller)<br />

Product display mode - Communication just between indoor unit and remote controller enabled (upon turning on of power)<br />

Timer short-circuited out (always)<br />

Imposes thermostat OFF on indoor unit<br />

97

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!