16.04.2015 Views

MULTI TYPE

MULTI TYPE

MULTI TYPE

SHOW MORE
SHOW LESS

Create successful ePaper yourself

Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.

Using indoor unit indicators (receiving unit light block) (wireless type)<br />

To identify the check code, check the 7-segment display on the header unit. To check for check codes not<br />

displayed on the 7-segment display, consult the “List of Check Codes (Indoor Unit)” in “8-2. Troubleshooting<br />

Method”.<br />

: Goes off : Lighting : Blinking (0.5 seconds)<br />

Light block Check code Cause of fault<br />

Operation Timer<br />

All lights out<br />

Ready<br />

– Power turned off or error in wiring between receiving and indoor units<br />

Operation Timer<br />

Ready<br />

E01<br />

E02<br />

E03<br />

Faulty reception<br />

Faulty transmission<br />

Loss of communication<br />

Receiving unit<br />

Error or poor contact in wiring<br />

between receiving and indoor<br />

units<br />

Blinking<br />

E08<br />

E09<br />

Duplicated indoor unit No. (address)<br />

Duplicated master remote controller<br />

Setting error<br />

E10<br />

Indoor unit inter-MCU communication error<br />

E12<br />

Automatic address starting error<br />

E18<br />

Error or poor contact in wiring between indoor units, indoor power turned off<br />

Operation Timer<br />

Ready<br />

E04<br />

Error or poor contact in wiring between indoor and outdoor units<br />

(loss of indoor-outdoor communication)<br />

E06<br />

Faulty reception in indoor-outdoor communication (dropping out of indoor unit)<br />

Blinking<br />

E07<br />

E15<br />

Faulty transmission in indoor-outdoor communication<br />

Indoor unit not found during automatic address setting<br />

E16<br />

Too many indoor units connected/overloading<br />

E19<br />

Error in number of outdoor header units<br />

E20<br />

Detection of refrigerant piping communication error during automatic address setting<br />

E23<br />

Faulty transmission in outdoor-outdoor communication<br />

E25<br />

Duplicated follower outdoor address<br />

E26<br />

Faulty reception in outdoor-outdoor communication, dropping out of outdoor unit<br />

E28<br />

Outdoor follower unit error<br />

E31<br />

IPDU communication error<br />

Operation Timer<br />

Ready<br />

P01<br />

P10<br />

Indoor AC fan error<br />

Indoor overflow error<br />

P12<br />

Indoor DC fan error<br />

Alternate blinking<br />

Operation Timer Ready<br />

Alternate blinking<br />

P13<br />

P03<br />

P04<br />

P05<br />

P07<br />

P15<br />

P17<br />

P18<br />

P19<br />

P20<br />

P22<br />

P26<br />

P29<br />

P31<br />

Outdoor liquid backflow detection error<br />

Outdoor discharge (TD1) temperature error<br />

Activation of outdoor high-pressure SW<br />

Open phase/power failure<br />

Inverter DC voltage (Vdc) error<br />

MG-CTT error<br />

Outdoor heat sink overheating error - Poor cooling of electrical component (IGBT) of outdoor unit<br />

Gas leak detection - insufficient refrigerant charging<br />

Outdoor discharge (TD2) temperature error<br />

Outdoor discharge (TD3) temperature error<br />

Outdoor 4-way valve reversing error<br />

Activation of high-pressure protection<br />

Outdoor fan IPDU error<br />

Outdoor G-Tr short-circuit error<br />

Compressor position detection circuit error<br />

Shutdown of other indoor unit in group due to fault (group follower unit error)<br />

MG-CTT: Magnet contactor<br />

175