NO. Item Specification outline Remarks<br />

14<br />

Filter sign<br />

display<br />

(not applicable<br />

to wireless type)<br />

* Provided in<br />

the separately<br />

mounted type,<br />

TCB-AX21E.<br />

1. The indoor fan’s cumulative hours of operation are counted, and when these<br />

exceed the prescribed value (150H/2500H), a filter replacement signal is sent to<br />

the remote controller to display a filter sign on it.<br />

2. When a filter reset signal is received from the remote controller, the timer<br />

measuring cumulative hours is cleared. If the prescribed hours have been<br />

exceeded, the hours count is reset, with the sign on the remote controller display<br />

erased.<br />

Filter service life 2500H 150H<br />

Type<br />

4-way air discharge cassette type<br />

1-way air discharge cassette type<br />

(SH, YH)<br />

2-way air discharge cassette type<br />

Under ceiling type<br />

Concealed duct standard type<br />

Concealed duct high static<br />

pressure type<br />

Slim duct type<br />

High wall type<br />

Floor standing type<br />

Floor standing concealed<br />

type<br />

Floor standing cabinet type<br />

“FILTER<br />

” displayed<br />

Operation<br />

standby<br />

Heating standby<br />

.......... Displayed on remote controller<br />

1. When any of the DN codes listed below is displayed<br />

• “P05” - Detection of an open phase in the power supply wiring<br />

• “P10” - Detection of indoor flooding in at least one indoor unit<br />

• “L30” - Detection of an interlock alarm in at least one indoor unit<br />

2. Forced thermo OFF<br />

• “COOL/DRY” operation is unavailable because at least one indoor unit is<br />

operating in “HEAT” mode.<br />

• “HEAT” operation is unavailable because at least one indoor unit is operating in<br />

“COOL/DRY” mode under priority cooling setting (bit 1 of SW11 on outdoor I/F<br />

P.C. board ON).<br />

3. All indoor units not able to engage in any of the above operations stand by in<br />

thermo OFF state.<br />

4. The indoor fan has been turned off because the system is engaged in a heat<br />

refrigerant (oil) recovery operation.<br />

.......... Displayed on remote controller<br />

1. Normal thermo OFF<br />

• During heating, the indoor unit goes thermo OFF as the heating temperature<br />

setting is reached.<br />

2. During heating, the fan rotates at a breeze speed (UL or lower) or remains<br />

stationary to prevent cold air from being discharged (including defrosting<br />

operation).<br />

3. Forced thermo OFF<br />

• “HEAT” operation is unavailable because at least one indoor unit is operating in<br />

“COOL/DRY” mode under priority cooling setting (bit 1 of SW11 on outdoor I/F<br />

P.C. board ON).<br />

• “OPERATION<br />

STANDBY ”<br />

displayed<br />

No display provided<br />

on wireless remote<br />

controller<br />

15<br />

• “HEATING<br />

STANDBY ”<br />

displayed<br />

74