8-5. Diagnosis procedure for each check code<br />

Check code Check code name<br />

Cause<br />

[E02] / [–]<br />

(AI-NET)<br />

Signal transmission error on the<br />

remote controller<br />

Unable to send signals to indoor units<br />

* The check code is not indicated on the central control device or the 7-segment indication on the outdoor unit.<br />

The<br />

communication wiring<br />

between the remote<br />

controller and indoor units<br />

is connected properly.<br />

No<br />

Connect the wiring properly.<br />

Yes<br />

The transmission circuit in the<br />

remote controller malfunctions.<br />

➝ Replace the remote controller.<br />

Check code Check code name<br />

Cause<br />

[E03] / [97]<br />

(AI-NET)<br />

Communication error between the<br />

indoor unit and remote controller<br />

(detected on the indoor unit)<br />

No communication from the remote<br />

controller/communication adapter<br />

The error is detected when the indoor unit cannot receive the signal from the wired remote controller.<br />

Check the communication wiring from the remote controller A and B.<br />

The check code [E03] is not indicated on the remote controller as its communication is down.<br />

However, the code is indicated on the compliant manager of TCC-LINK.<br />

Check code Check code name<br />

Cause<br />

[E01] / [–]<br />

(AI-NET)<br />

Communication error between the<br />

indoor unit and remote controller<br />

(detected on the remote<br />

controller)<br />

1. Remote controller inter-unit wire error<br />

2. Indoor power error<br />

3. Indoor P.C. board error<br />

4. Remote controller address setup error<br />

5. Remote controller P.C. board error<br />

Is the<br />

inter-unit wire of<br />

remote controllers (A/B)<br />

normal?<br />

Yes<br />

No<br />

Correct inter-unit cable of<br />

remote controller.<br />

Is there no<br />

disconnection or<br />

connector contact error on<br />

harness out of terminal<br />

block of indoor<br />

unit?<br />

Yes<br />

Correct connector connection<br />

and check circuit wiring.<br />

No<br />

Is a group control<br />

operation?<br />

No<br />

Yes<br />

Is power of each indoor<br />

unit turned on?<br />

No<br />

Check power connection<br />

status of indoor unit. (Turn on<br />

power again.)<br />

Yes<br />

Is power applied<br />

to remote controller?<br />

AB terminals: Approx.<br />

DC18V<br />

No<br />

Check indoor P.C. board.<br />

Defect ➝ Replace<br />

Yes<br />

Is setup of two<br />

remote controllers<br />

without header remote<br />

controller?<br />

Yes<br />

Change one to header/other to<br />

follower. (Remote controller<br />

address connector)<br />

No<br />

Check remote controller P.C.<br />

board.<br />

Defect ➝ Replace<br />