NO. Item Specification outline Remarks<br />

5<br />

Fan speed<br />

control<br />

1. The fan operates in one of the four speed modes of “HIGH (HH)”, “MED (H)”,<br />

“LOW (L)” and “AUTO” on the basis of a command issued via the remote<br />

controller. (Concealed duct high static pressure type: HH only)<br />

2. In AUTO fan speed mode, the air speed changes according to the difference<br />

between Ta and Ts.<br />

<br />

Ta (°C)<br />

+3.0<br />

+2.5<br />

+2.0<br />

+1.5<br />

+1.0<br />

+0.5<br />

Tsc<br />

-0.5<br />

HH<br />

H+<br />

H<br />

L+<br />

L<br />

L<br />

L<br />

<br />

<br />

<br />

<br />

<br />

<br />

<br />

• Control is identical in remote controller thermo and body thermo operation.<br />

Speed modes shown in < > apply to cooling operation under AUTO air<br />

conditioner operation mode.<br />

• In AUTO fan speed mode, the fan speed remains the same for 3 minutes each<br />

time a speed change occurs.<br />

However, a speed change command issued via the remote controller can<br />

override this, and the fan speed changes accordingly.<br />

• At the beginning of cooling operation, a higher speed (steeper downward<br />

temperature gradient) is chosen.<br />

• As long as the temperature difference remains on a boundary line, the fan speed<br />

stays the same.<br />

<br />

(-0.5)<br />

(0)<br />

Ta (°C)<br />

-1.0<br />

Tsh<br />

(+0.5) +1.0<br />

(+1.0) +2.0<br />

(+1.5) +3.0<br />

(+2.0) +4.0<br />

L<br />

L+<br />

H<br />

H+<br />

<br />

<br />

<br />

<br />

HH <br />

Figures inside ( ) applies to remote controller thermo operation.<br />

Figures outside ( ) applies to body thermo operation.<br />

Speed modes shown in < > apply to heating operation under AUTO air<br />

conditioner operation mode.<br />

• In AUTO fan speed mode, the fan speed remains the same for 1 minute each<br />

time a speed change occurs.<br />

However, a speed change command issued via the remote controller can<br />

override this, and the fan speed changes accordingly.<br />

• At the beginning of heating operation, a higher speed (steeper upward<br />

temperature gradient) is chosen.<br />

• As long as the temperature difference remains on a boundary line, the fan speed<br />

stays the same.<br />

• When TC2 60 °C, the fan speed is raised by one step.<br />

3. If the air conditioner goes thermo OFF during heating operation, the fan speed<br />

drops down to LL (breeze).<br />

A<br />

B<br />

C<br />

D<br />

E<br />

F<br />

G<br />

E<br />

D<br />

C<br />

B<br />

A<br />

HH > H+ > H ><br />

L+ > L > UL<br />

or LL<br />

DN code “32”<br />

“0000”: Body thermo<br />

“0001”: Remote<br />

controller thermo<br />

TC2: Indoor heat<br />

exchanger sensor<br />

temperature<br />

“HEATING<br />

STANDBY ”<br />

displayed<br />