Check code Check code name<br />

Cause<br />

[E18] / [97•99]<br />

(AI-NET)<br />

Communication error between<br />

indoor header and follower<br />

Regular communication between indoor header and<br />

follower is unavailable.<br />

Are remote<br />

controller inter-unit wires<br />

(A/B) normal?<br />

No<br />

Correct remote controller<br />

inter-unit wire.<br />

Yes<br />

Is there any<br />

disconnection of<br />

connector or wiring from<br />

terminal block of<br />

indoor unit?<br />

Yes<br />

Correct connection of<br />

connector.<br />

Check circuit wire.<br />

No<br />

Is group<br />

control operation<br />

executed?<br />

No<br />

Yes<br />

Are powers of all indoor<br />

units turned on?<br />

No<br />

Check power connection<br />

status of indoor unit. (Turn<br />

on the power again.)<br />

Yes<br />

Check indoor address.<br />

Check indoor P.C. board.<br />

Failure ➝ Replace<br />

Correct indoor address.<br />

Check code Check code name<br />

Cause<br />

[E16] / [89]<br />

(AI-NET)<br />

Number/capacity of connected<br />

indoor units beyond the limit<br />

1. There are 48 or more connected indoor units.<br />

2. Capacity over of total connected indoor units.<br />

3. Incorrect setup of indoor units' power<br />

Sub-code: 00 : Capacity over, 01-: number of connected units<br />

Is backup<br />

operation of outdoor unit<br />

being set up?<br />

No<br />

Yes<br />

Indoor capacity over has been<br />

detected during the backup<br />

operation.<br />

Perform setup of no detection for<br />

capacity over. (*1)<br />

Is No. of connected<br />

indoor units correct?<br />

No<br />

Excessive indoor units are<br />

connected.<br />

Correct miswiring.<br />

Yes<br />

Is setup of indoor<br />

units' HP correct?<br />

No<br />

Correct HP setup.<br />

Yes<br />

Is total capacity<br />

of connected indoor<br />

units within 135%?<br />

No<br />

Set capacity of connected indoor<br />

units within 135% of outdoor units.<br />

Yes<br />

For a service<br />

P.C. board, check<br />

outdoor HP setup.<br />

(Set up jumper 9, 10, 11,<br />

and 12.)<br />

OK<br />

Set up outdoor HP.<br />

(Refer “13 P.C. BOARD<br />

EXCHANGE PROCEDURES”.)<br />

NG<br />

Check outdoor interface<br />

P.C. board.<br />

(*1) To deactivate the capacity-over detection<br />

Turn SW09 Bit 2 on I/F P.C. board of header outdoor unit to ON.<br />

(Usually OFF)<br />

198