▼ Leaving-ON prevention control<br />

[Function]<br />

• This function controls the indoor units individually. It is connected with cable to the control P.C. board of the<br />

indoor unit.<br />

• In a group control, it is connected with cable to the indoor unit (Control P.C. board), and the CODE No. 2E<br />

is set to the connected indoor unit.<br />

• It is used when the start operation from outside if unnecessary but the stop operation is necessary.<br />

• Using a card switch box, card lock, etc, the forgotten-OFF of the indoor unit can be protected.<br />

• When inserting a card, start/stop operation from the remote controller is allowed.<br />

• When taking out a card, the system stops if the indoor unit is operating and start/stop operation from the<br />

remote controller is forbidden.<br />

1. Control items<br />

1) Outside contact ON: The start/stop operation from the remote controller is allowed.<br />

(Status that card is inserted in the card switch box)<br />

2) Outside contact OFF: If the indoor unit is operating, it is stopped forcedly.<br />

(Start/Stop prohibited to remote controller)<br />

(Status that card is taken out from the card switch box)<br />

* When the card switch box does not perform the above contact operation, convert it using a relay with b<br />

contact.<br />

2. Operation<br />

Handle the wired remote controller switch in the following procedure.<br />

* Use the wired remote controller switch during stop of the system.<br />

1 Push concurrently + + buttons for 4 seconds or more.<br />

2 Using the setup temp or button, specify the CODE No. .<br />

3 Using the timer time or button, set to the SET DATA.<br />

4 Push button.<br />

5 Push button. (The status returns to the usual stop status.)<br />

3. Wiring<br />

CN61<br />

T10<br />

(YEL)<br />

1 1<br />

2 2<br />

3 3<br />

4 4<br />

5 5<br />

6 6<br />

Relay (procured locally)<br />

* In the figure, the contact indicates<br />

a status that the card is taken out.<br />

Indoor control P.C. board<br />

Note) Determine the cable length between the indoor control P.C. board and the relay within 2m.<br />

▼ Power peak-cut from indoor unit<br />

When the relay is turned on, a forced thermostat-OFF operation starts.<br />

Power supply<br />

Outside contact (Card switch box, etc: Procured locally)<br />

• Wiring example<br />

CN73<br />

EXCT<br />

(2P plug: RED)<br />

1<br />

2<br />

1<br />

2<br />

Relay (procured locally)<br />

Relay coil signal<br />

Note) Determine the cable length between the indoor or<br />

outdoor control P.C. board and the relay within 2m.<br />

Indoor control P.C. board<br />

105