9-4. Cooling-Season Outdoor Unit Backup Operation<br />

Setting<br />

<br />

Limited to summer and other situations where there is no need for heating operation, this function makes it possible<br />

to get backup operation up and running quickly without going through the normal setup procedure, regardless of<br />

which type of outdoor unit has failed, the header unit or a follower unit.<br />

In this backup operation, the system behaves in exactly the same way as described in the “Outdoor Unit Backup<br />

Operation Setting” section, except that it cannot perform heating operation.<br />

Note 1: When the system is set up for this function, heating operation is not available.<br />

(The HEAT mode on the remote controller cannot be selected.)<br />

Note 2: If the unit failure has been caused by a fault in the interface P.C. board or electric circuit, this function is<br />

not available. In that case, follow the procedure specified in the “Outdoor Unit Backup Operation Setting”<br />

section.<br />

<br />

(1) Turn off the power supply to all the units connected to the system.<br />

[Setup of failed outdoor unit]<br />

Regardless of whether the failed outdoor unit is the header unit or a follower unit, there is no difference in the setup<br />

procedure.<br />

(2) Turn on Bits 1, 2 and 3 of SW06 provided on the interface P.C. board.<br />

(3) If there is a leakage from an outdoor PMV (unable to close), fully close the liquid pipe service valve.<br />

(4) Turn on the power supply to all the units connected to the system.<br />

If the fault involves poor insulation of a compressor motor, remove the compressor leads before the power is<br />

turned on.<br />

Turn on Bits 1, 2 and 3 of SW06.<br />

SW06 SW07 SW09 SW10<br />

1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4<br />

SW11<br />

SW12<br />

SW13<br />

SW14<br />

1 2 3 4 1 2 3 4 1 2 3 4 1 2 3 4<br />

SW16<br />

SW17<br />

1 2 3 4 1 2 3 4<br />

This is the end of cooling-season outdoor unit backup operation setting.<br />