(C)<br />

Heating operation<br />

Does heating<br />

indoor fan normally<br />

operate?<br />

Yes<br />

Is indoor PMV<br />

normal?<br />

Yes<br />

Is check valve<br />

of main<br />

discharge pipe<br />

normal?<br />

Yes<br />

Is there any interference<br />

of heat-exchanging of<br />

indoor unit?<br />

1. Filter clogging<br />

2. Heat exchanger<br />

clogging<br />

3. Air short circuit<br />

No<br />

Is SV5 circuit normal?<br />

Yes<br />

Are any indoor<br />

units in different<br />

refrigerant circuit<br />

connected?<br />

No<br />

Refrigerant overcharge,<br />

clogging, pipe breakage,<br />

abnormal overload<br />

No<br />

No<br />

Is connector<br />

connection and coil<br />

normal?<br />

No<br />

Yes<br />

Yes<br />

Is there<br />

clogging in any<br />

valves?<br />

No<br />

No<br />

Yes<br />

Is connector<br />

connection, condenser<br />

or fan motor normal?<br />

No<br />

Yes<br />

No<br />

Yes<br />

Are<br />

characteristics of<br />

sensor TC2 and TCJ<br />

resistance normal?<br />

(Check it using the<br />

miswiring check function<br />

of the outdoor unit.)<br />

No<br />

Yes<br />

Check indoor P.C. board.<br />

Faulty ➝ Replace<br />

Repair faulty parts.<br />

Repair faulty parts.<br />

Repair check valve.<br />

➝ Replace<br />

Eliminate the<br />

interference.<br />

Replace PMV body.<br />

Repair SV5 circuit.<br />

(Coil error, choke,<br />

disconnection of cables, etc.)<br />

Check and correct<br />

wiring.<br />

Replace TC2 or TCJ<br />

sensor.<br />

Check code Check code name<br />

Cause<br />

[P20] / [22]<br />

(AI-NET)<br />

High-pressure protective<br />

operation<br />

1. Pd sensor error<br />

2. Service valve closed.<br />

3. Indoor/outdoor fan error<br />

4. Indoor/outdoor PMV clogging<br />

5. Indoor/outdoor heat exchanger clogging<br />

6. SV2 circuit error<br />

7. SV4 circuit error<br />

8. SV5 circuit error<br />

9. Outdoor I/F P.C. board error<br />

10. Operation error of check valve of main discharge<br />

pipe<br />

11. Refrigerant overcharge<br />

Are service valves fully<br />

opened?<br />

No<br />

Open service valves fully.<br />

Yes<br />

Are<br />

characteristics of highpressure<br />

sensor<br />

normal?<br />

Yes<br />

No<br />

Reset power supply, and start a test operation<br />

corresponded to the season.<br />

Cooling operation (B)<br />

Cooling ➝ To (B)<br />

Heating ➝ To (C)<br />

Check parts.<br />

Failure ➝ Replace<br />

* 1. Pressure by pressure gauge (Check joint)<br />

2. Pressure display on 7-segment display<br />

3. Output voltage of I/F P.C. board<br />

If 1 and 2, 3 are different, an error of pressure sensor<br />

is considered.<br />

If 2 and 3 are different, check I/F P.C. board.<br />

Does<br />

cooling outdoor fan<br />

normally operate?<br />

Yes<br />

No<br />

Repair faulty parts.<br />

Is there<br />

any fan crack<br />

or coming-off?<br />

No<br />

Is outdoor PMV normal?<br />

1. Connector connection<br />

2. Wiring<br />

3. Coil<br />

4. Valve body<br />

5. Outdoor I/F P.C. board<br />

Yes<br />

No<br />

Connectors: PMV1: CN300,<br />

PMV2: CN301, PMV4: CN303<br />

Repair faulty parts.<br />

(Connector connection, fan IPDU,<br />

fan motor, cabling)<br />

Repair outdoor PMV.<br />

Yes<br />

Is there any<br />

interference of heatexchanging<br />

of outdoor unit?<br />

1. Heat exchanger clogging<br />

2. Air short circuit<br />

Yes<br />

Eliminate the interference.<br />

No<br />

Is SV2 bypass<br />

circuit normal?<br />

No<br />

Repair SV2 bypass circuit.<br />

Yes<br />

(Coil error, clogging, disconnection<br />

of wire, etc.)<br />

Is SV4 circuit normal?<br />

No<br />

Repair SV4 circuit.<br />

Yes<br />

(Coil error, clogging, disconnection<br />

of wire, etc.)<br />

Is check valve of<br />

main discharge pipe<br />

normal?<br />

Yes<br />

No<br />

Repair check valve. ➝ Replace<br />

Refrigerant overcharge, clogging, pipe<br />

breakage, abnormal overload<br />

222