Main<br />

remote<br />

controller<br />

P04<br />

P05<br />

P07<br />

P10<br />

Check code<br />

Outdoor 7-segment display<br />

Check<br />

code<br />

P04<br />

P05<br />

P07<br />

P10<br />

Sub-code<br />

01: Compressor<br />

1 side<br />

02: Compressor<br />

2 side<br />

03: Compressor<br />

3 side<br />

00:<br />

01: Compressor<br />

1 side<br />

02: Compressor<br />

2 side<br />

03: Compressor<br />

3 side<br />

01: Compressor<br />

1 side<br />

02: Compressor<br />

2 side<br />

03: Compressor<br />

3 side<br />

Detected indoor<br />

address<br />

AI-NET central<br />

control<br />

remote<br />

controller<br />

21<br />

AF<br />

1C<br />

0b<br />

P12 – – 11<br />

Location<br />

of<br />

detection<br />

IPDU<br />

I/F<br />

IPDU<br />

I/F<br />

Indoor<br />

unit<br />

Indoor<br />

unit<br />

Description<br />

Activation of highpressure<br />

SW<br />

Detection of open<br />

phase/phase sequence<br />

Inverter DC voltage<br />

(Vdc) error<br />

(compressor)<br />

MG-CTT error<br />

Heat sink overheating<br />

error<br />

System<br />

status<br />

All stop<br />

All stop<br />

All stop<br />

Error detection<br />

condition(s)<br />

High-pressure SW is<br />

activated.<br />

• Open phase is<br />

detected when<br />

power is turned<br />

on.<br />

• Inverter DC<br />

voltage is too high<br />

(overvoltage) or<br />

too low<br />

(undervoltage).<br />

Temperature sensor<br />

built into IGBT (TH)<br />

is overheated.<br />

Indoor overflow error All stop • Float switch<br />

operates.<br />

• Float switch circuit<br />

is open-circuited<br />

or disconnected at<br />

connector.<br />

Indoor fan motor error<br />

Stop of<br />

corresponding<br />

unit<br />

• Motor speed<br />

measurements<br />

continuously<br />

deviate from target<br />

value.<br />

• Overcurrent<br />

protection is<br />

activated.<br />

Check items (locations)<br />

• Check connection of highpressure<br />

SW connector.<br />

• Check for defect in Pd<br />

pressure sensor.<br />

• Check outdoor service valves<br />

(gas side, liquid side) to<br />

confirm full opening.<br />

• Check for defect in outdoor<br />

fan.<br />

• Check for defect in outdoor<br />

fan motor.<br />

• Check outdoor PMVs (PMV1,<br />

2) for clogging.<br />

• Check indoor/outdoor heat<br />

exchangers for clogging.<br />

• Check for short-circuiting of<br />

outdoor suction/discharge air<br />

flows.<br />

• Check SV2 circuit for<br />

clogging.<br />

• Check for defect in outdoor<br />

P.C. board (I/F).<br />

• Check for error in indoor fan<br />

system (possible cause of air<br />

flow reduction).<br />

• Check opening status of<br />

indoor PMV.<br />

• Check indoor-outdoor<br />

communication line for wiring<br />

error.<br />

• Check for faulty operation of<br />

check valve in discharge pipe<br />

convergent section.<br />

• Check gas balancing SV4<br />

valve circuit.<br />

• Check SV5 valve circuit.<br />

• Check for refrigerant<br />

overcharging.<br />

• Check for defect in outdoor<br />

P.C. board (I/F).<br />

• Check power supply voltage.<br />

• Check outdoor fan system<br />

error.<br />

• Check heat sink cooling duct<br />

for clogging.<br />

• Check IGBT and heat sink for<br />

thermal performance for faulty<br />

installation.<br />

(e.g. mounting screws and<br />

thermal conductivity)<br />

• Check for defect in A3-IPDU.<br />

(faulty IGBT built-in<br />

temperature sensor (TH))<br />

• Check float switch connector.<br />

• Check operation of drain<br />

pump.<br />

• Check drain pump circuit.<br />

• Check drain pipe for clogging.<br />

• Check for defect in indoor<br />

P.C. board.<br />

• Check connection of fan<br />

connector and wiring.<br />

• Check for defect in fan motor.<br />

• Check for defect in indoor<br />

P.C. board.<br />

• Check impact of outside air<br />

treatment (OA).<br />

MG-CTT: Magnet contactor<br />

188