Check code Check code name Cause<br />

Check code Check code name<br />

Cause<br />

[E06] / [04]<br />

(AI-NET)<br />

Decreased number of indoor units [E04] / [04] Indoor/Outdoor communication<br />

1. Communication lines (U1, U2) connection error<br />

between indoor and outdoor<br />

2. Communication connector's connection error on<br />

indoor unit, error on P.C. board<br />

3. Communication connector's connection error on<br />

outdoor unit, error on I/F board<br />

4. Power supply of indoor unit (Is power turned on?)<br />

(AI-NET)<br />

circuit error<br />

(Detected at indoor side)<br />

1. Power of outdoor unit was firstly turned on.<br />

2. Connection error of communication line between<br />

indoor and outdoor<br />

3. End terminal resistance setup error on<br />

communication between indoor and outdoor<br />

4. Address setup error<br />

Sub-code: No. of indoor units which received signals normally<br />

Is there no<br />

miswiring/disconnection<br />

on communication line<br />

between indoor and<br />

outdoor?<br />

No<br />

Is connection<br />

of CN40 connector on<br />

indoor P.C. board<br />

normal?<br />

Yes<br />

No<br />

Correct communication line.<br />

Correct wiring or connector.<br />

Was power turned on<br />

in order of indoor unit<br />

➝ outdoor unit?<br />

Yes<br />

Is connection<br />

(U1/U2 terminals) of<br />

indoor/outdoor inter-unit<br />

wire normal?<br />

Yes<br />

No<br />

No<br />

Turn on power again in order<br />

of indoor unit ➝ outdoor unit.<br />

Correct inter-unit wire.<br />

Yes<br />

Is connection of CN01<br />

connector on outdoor I/F<br />

P.C. board normal?<br />

No<br />

Is connector<br />

connection from U1/U2<br />

terminals of indoor/outdoor<br />

inter-unit wire<br />

normal?<br />

Yes<br />

No<br />

Correct connector connection.<br />

Yes<br />

Is the end terminal<br />

resistance setup of outdoor<br />

unit normal?<br />

No<br />

Correct the end terminal<br />

resistance setup.<br />

Is power of indoor unit<br />

turned on?<br />

No<br />

Turn on power of indoor unit.<br />

Yes<br />

Yes<br />

No<br />

Is address setup correct?<br />

Set up address again.<br />

Did a power failure<br />

occur?<br />

No<br />

Is there no noise, etc?<br />

Yes<br />

Yes<br />

Clear the check code.<br />

Check noise, etc, and eliminate<br />

it if any.<br />

Yes<br />

Is power applied to fuse<br />

(F03) on indoor P.C.<br />

board?<br />

Yes<br />

No<br />

Check connection of inter-unit<br />

wire between indoor and outdoor<br />

is correct, and then connect<br />

communication line connector on<br />

indoor P.C. board (CN40) to<br />

CN44 (EMG).<br />

No<br />

Is there no noise, etc?<br />

Yes<br />

Check noise, etc, and<br />

eliminate it if any.<br />

Check indoor P.C. board.<br />

Defect ➝ Replace<br />

(NOTE)<br />

1. When signal is not sent for a certain period from the indoor unit which has<br />

used to send signals normally, [E06] is displayed.<br />

No<br />

Check indoor P.C. board.<br />

Defect ➝ Replace<br />

For details, refer to “7-5. Troubleshooting in Test Operation”.<br />