(Error detected by main remote controller)<br />

Main<br />

remote<br />

controller<br />

AI-NET central<br />

control display<br />

(with use of<br />

network<br />

adaptor)<br />

Check code<br />

Outdoor 7-segment display<br />

Sub-code<br />

E01 97 – –<br />

E02 – – –<br />

E09 99 – –<br />

Display of receiving unit<br />

Indicator light block<br />

Operation Timer Ready<br />

Flash<br />

Typical fault site<br />

No master remote controller,<br />

faulty remote controller<br />

communication (reception)<br />

Faulty remote controller<br />

communication (transmission)<br />

Duplicated master remote<br />

controller<br />

Description of error<br />

Signals cannot be received from indoor unit;<br />

master remote controller has not been set<br />

(including two remote controller control).<br />

Signals cannot be transmitted to indoor unit.<br />

Both remote controllers have been set as<br />

master remote controller in two remote<br />

controller control (alarm and shutdown for<br />

header unit and continued operation for<br />

follower unit)<br />

(Error detected by central control device)<br />

TCC-LINK<br />

central<br />

control<br />

AI-NET central<br />

control display<br />

(with use of<br />

network<br />

adaptor)<br />

Check code<br />

Outdoor 7-segment display<br />

Sub-code<br />

C05 98 – –<br />

C06 97 – –<br />

Display of receiving unit<br />

Indicator light block<br />

Operation Timer Ready<br />

Flash<br />

No indication (when<br />

main remote controller<br />

also in use)<br />

Typical fault site<br />

Faulty central control<br />

communication (transmission)<br />

Faulty central control<br />

communication (reception)<br />

– 99 – – Multiple network adapters<br />

C12 23 – – –<br />

P30 b7 – –<br />

As per alarm unit (see<br />

above)<br />

Blanket alarm for generalpurpose<br />

device control<br />

interface<br />

Group control follower unit<br />

error<br />

Description of error<br />

Central control device is unable to transmit<br />

signal due to duplication of central control<br />

device (AI-NET).<br />

Central control device is unable to receive<br />

signal.<br />

Multiple network adapters are connected to<br />

remote controller communication line (AI-<br />

NET).<br />

Device connected to general-purpose device<br />

control interface for TCC-LINK/AI-NET is<br />

faulty.<br />

Group follower unit is faulty (unit No. and<br />

above detail [] displayed on main remote<br />

controller)<br />

Note: The same error, e.g. a communication error, may result in the display of different check codes depending on the device that detects it.<br />

Moreover, check codes detected by the main remote controller/central control device do not necessarily have a direct impact on air<br />

conditioner operation.<br />