(Errors detected by IPDU featuring in SMMS-i standard outdoor unit - typical examples)<br />

F13<br />

H01<br />

H02<br />

H03<br />

P04<br />

P07<br />

P22<br />

P26<br />

P29<br />

Check code<br />

Outdoor 7-segment display<br />

Sub-code<br />

01: Compressor 1<br />

02: Compressor 2<br />

03: Compressor 3<br />

01: Compressor 1<br />

02: Compressor 2<br />

03: Compressor 3<br />

01: Compressor 1<br />

02: Compressor 2<br />

03: Compressor 3<br />

01: Compressor 1<br />

02: Compressor 2<br />

03: Compressor 3<br />

01: Compressor 1<br />

02: Compressor 2<br />

03: Compressor 3<br />

01: Compressor 1<br />

02: Compressor 2<br />

03: Compressor 3<br />

0: IGBT circuit<br />

1: Position detection circuit error<br />

3: Motor lockup error<br />

4: Motor current detection<br />

C: TH sensor error<br />

D: TH sensor error<br />

E: Inverter DC voltage error<br />

(outdoor fan)<br />

Note: Although letters 0 to F appear<br />

at locations indicated by “”,<br />

please ignore them.<br />

01: Compressor 1<br />

02: Compressor 2<br />

03: Compressor 3<br />

01: Compressor 1<br />

02: Compressor 2<br />

03: Compressor 3<br />

TCC-LINK<br />

central control<br />

or main remote<br />

controller<br />

display<br />

F13<br />

H01<br />

H02<br />

H03<br />

P04<br />

P07<br />

Display of receiving unit<br />

Indicator light block<br />

Operation Timer Ready<br />

Flash<br />

ALT<br />

ALT<br />

ALT<br />

Typical fault site<br />

Error in temperature<br />

sensor built into indoor<br />

IGBT (TH)<br />

Compressor breakdown<br />

Description of error<br />

Temperature sensor built into indoor IGBT (TH)<br />

has been open/short-circuited.<br />

Inverter current (Idc) detection circuit detects<br />

overcurrent.<br />

Compressor error (lockup) Compressor lockup is detected<br />

Current detection circuit<br />

error<br />

Activation of high-pressure<br />

SW<br />

Heat sink overheating<br />

error<br />

Abnormal current is detected while inverter<br />

compressor is turned off.<br />

High-pressure SW is activated.<br />

Temperature sensor built into IGBT (TH) detects<br />

overheating.<br />

P22 ALT Outdoor fan IPDU error Outdoor fan IPDU detects error.<br />

P26<br />

P29<br />

ALT<br />

ALT<br />

Activation of G-Tr (IGBT)<br />

short-circuit protection<br />

Compressor position<br />

detection circuit error<br />

Short-circuit protection for compressor motor<br />

driver circuit components is activated (momentary<br />

overcurrent).<br />

Compressor motor position detection error is<br />

detected.<br />

Note: The above check codes are examples only, and different check codes may be displayed depending on the outdoor unit configuration<br />