Errors Detected by TCC-LINK Central Control Device<br />

Main<br />

remote<br />

controller<br />

Check code<br />

Outdoor 7-segment display<br />

Sub-code<br />

AI-NET central<br />

control<br />

remote<br />

controller<br />

C05 – –<br />

C06 – –<br />

C12 – –<br />

P30<br />

Differs according to<br />

nature of alarm-causing<br />

error<br />

(L20 displayed.)<br />

Location<br />

of<br />

detection<br />

TCC-LINK<br />

Generalpurpose<br />

device<br />

I/F<br />

TCC-LINK<br />

Description<br />

TCC-LINK<br />

central control<br />

device<br />

transmission<br />

error<br />

TCC-LINK<br />

central control<br />

device reception<br />

error<br />

Blanket alarm<br />

for generalpurpose<br />

device<br />

control interface<br />

Group control<br />

follower unit<br />

error<br />

Duplicated<br />

central control<br />

address<br />

System status<br />

Continued<br />

operation<br />

Continued<br />

operation<br />

Continued<br />

operation<br />

Continued<br />

operation<br />

Continued<br />

operation<br />

Error detection<br />

condition(s)<br />

Central control device is<br />

unable to transmit signal.<br />

Central control device is<br />

unable to receive signal.<br />

Error signal is input to control<br />

interface for general-purpose<br />

devices.<br />

Error occurs in follower unit<br />

under group control.<br />

([P30] is displayed on central<br />

control remote controller.)<br />

There is duplication in central<br />

control addresses.<br />

Check items (locations)<br />

• Check for defect in central<br />

control device.<br />

• Check for defect in central<br />

control communication<br />

line.<br />

• Check termination<br />

resistance setting.<br />

• Check for defect in central<br />

control device.<br />

• Check for defect in central<br />

control communication<br />

line.<br />

• Check termination<br />

resistance setting.<br />

• Check power supply for<br />

devices at other end of<br />

central control<br />

communication line.<br />

• Check defect in P.C.<br />

boards of devices at other<br />

end of central control<br />

communication line.<br />

• Check error input.<br />

• Check check code of unit<br />

that has generated alarm.<br />

• Check address settings.<br />