MULTI TYPE
MULTI TYPE
MULTI TYPE
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Main<br />
remote<br />
controller<br />
Check code<br />
Outdoor 7-segment display<br />
Check<br />
code<br />
Sub-code<br />
AI-NET central<br />
control<br />
remote<br />
controller<br />
F08 F08 – 1b<br />
F10 – – 0C<br />
F11 – –<br />
F12 F12 – A2<br />
F13<br />
F13<br />
01: Compressor 1<br />
side<br />
02: Compressor 2<br />
side<br />
03: Compressor 3<br />
side<br />
43<br />
F15 F15 – 18<br />
F16 F16 – 43<br />
F22 F22 –<br />
F23 F23 – 43<br />
F24 F24 – 43<br />
Location<br />
of<br />
detection<br />
I/F<br />
Indoor<br />
unit<br />
Indoor<br />
unit<br />
I/F<br />
IPDU<br />
I/F<br />
I/F<br />
I/F<br />
I/F<br />
I/F<br />
Description<br />
TO sensor<br />
error<br />
Indoor TA<br />
sensor error<br />
Indoor TF<br />
sensor error<br />
TS1 sensor<br />
error<br />
TH sensor<br />
error<br />
Outdoor<br />
temperature<br />
sensor wiring<br />
error (TE1,<br />
TL)<br />
Outdoor<br />
pressure<br />
sensor wiring<br />
error (Pd, Ps)<br />
TD3 sensor<br />
error<br />
Ps sensor<br />
error<br />
Pd sensor<br />
error<br />
System<br />
status<br />
All stop<br />
Stop of<br />
corresponding<br />
unit<br />
Stop of<br />
corresponding<br />
unit<br />
All stop<br />
All stop<br />
All stop<br />
All stop<br />
All stop<br />
All stop<br />
All stop<br />
Error detection<br />
condition(s)<br />
Sensor resistance is infinity<br />
or zero (open/short circuit).<br />
Sensor resistance is infinity<br />
or zero (open/short circuit).<br />
Sensor resistance is infinity<br />
or zero (open/short circuit).<br />
Sensor resistance is infinity<br />
or zero (open/short circuit).<br />
Sensor resistance is infinity<br />
or zero (open/short circuit).<br />
During compressor<br />
operation in HEAT mode,<br />
TE1 continuously provides<br />
temperature reading<br />
higher than indicated by TL<br />
by at least specified margin<br />
for 3 minutes or more.<br />
Readings of high-pressure<br />
Pd sensor and lowpressure<br />
Ps sensor are<br />
switched.<br />
Output voltages of both<br />
sensors are zero.<br />
Sensor resistance is infinity<br />
or zero. (open/short circuit)<br />
Output voltage of Ps<br />
sensor is zero.<br />
Output voltage of Pd<br />
sensor is zero (sensor<br />
open-circuited).<br />
Pd > 4.15MPa despite<br />
compressor having been<br />
turned off.<br />
Check items (locations)<br />
• Check connection of TO<br />
sensor connector.<br />
• Check resistance<br />
characteristics of TO sensor.<br />
• Check for defect in outdoor<br />
P.C. board (I/F).<br />
• Check connection of TA<br />
sensor connector and wiring.<br />
• Check resistance<br />
characteristics of TA sensor.<br />
• Check for defect in indoor P.C.<br />
board.<br />
• Check connection of TF<br />
sensor connector and wiring.<br />
• Check resistance<br />
characteristics of TF sensor.<br />
• Check for defect in indoor P.C.<br />
board.<br />
• Check connection of TS1<br />
sensor connector.<br />
• Check resistance<br />
characteristics of TS1 sensor.<br />
• Check for defect in outdoor<br />
P.C. board (I/F).<br />
• Defect in IGBT built-in<br />
temperature sensor<br />
➝ Replace A3-IPDU P.C.<br />
board.<br />
• Check installation of TE1 and<br />
TL sensors.<br />
• Check resistance<br />
characteristics of TE1 and TL<br />
sensors.<br />
• Check for outdoor P.C. board<br />
(I/F) error.<br />
• Check connection of highpressure<br />
Pd sensor connector.<br />
• Check connection of lowpressure<br />
Ps sensor connector.<br />
• Check for defect in pressure<br />
sensors Pd and Ps.<br />
• Check for error in outdoor P.C.<br />
board (I/F).<br />
• Check for deficiency in<br />
compressive output of<br />
compressor.<br />
• Check connection of TD3<br />
sensor connector.<br />
• Check resistance<br />
characteristics of TD3 sensor.<br />
• Check for defect in outdoor<br />
P.C. board (I/F).<br />
• Check for connection error<br />
involving Ps sensor and Pd<br />
sensor connectors.<br />
• Check connection of Ps sensor<br />
connector.<br />
• Check for defect in Ps sensor.<br />
• Check for deficiency in<br />
compressive output of<br />
compressor.<br />
• Check for defect in 4-way<br />
valve.<br />
• Check for defect in outdoor<br />
P.C. board (I/F).<br />
• Check for defect in SV4 circuit.<br />
• Check connection of Pd<br />
sensor connector.<br />
• Check for defect in Pd sensor.<br />
• Check for defect in outdoor<br />
P.C. board (I/F).<br />
182