6-8-3. Snowfall Fan Control<br />

Header outdoor unit<br />

Outdoor unit<br />

interface PCB<br />

CN509<br />

Connection<br />

cable<br />

Optional PCB<br />

TB1<br />

COM<br />

PJ17 COOL<br />

HEAT<br />

Locally procured<br />

Shield<br />

wire<br />

Snowfall sensor<br />

SW1<br />

Operation<br />

An external snowfall signal turns on the outdoor unit fan.<br />

Terminal Input signal Operation<br />

COOL<br />

(SW1)<br />

SW1: Snowfall detection switch (snowfall sensor)<br />

ON<br />

OFF<br />

ON<br />

OFF<br />

Snowfall fan control<br />

(Turns on outdoor<br />

unit fan)<br />

Normal operation<br />

(Cancels control)<br />

The input signal is recognized during its rising/falling phase.<br />

(After reaching the top/bottom of the rising/falling edge, the signal must remain there for at least 100 ms.)<br />

The optional P.C. board should be connected to the header outdoor unit (U1).<br />

6-8-4. External master ON/OFF Control<br />

Header outdoor unit<br />

Outdoor unit<br />

interface PCB<br />

CN512<br />

SW1: Operation input switch<br />

SW2: Stop input switch<br />

Connection<br />

cable<br />

Operation<br />

The system is started/stopped from the outdoor unit.<br />

Optional PCB<br />

PJ17<br />

COM<br />

COOL<br />

HEAT<br />

TB1<br />

Locally procured<br />

Shield<br />

wire<br />

SW1<br />

SW2<br />

Terminal Input signal Operation<br />

COOL<br />

(SW1)<br />

ON<br />

OFF<br />

Turns on all indoor<br />

units<br />

HEAT<br />

(SW2)<br />

ON<br />

OFF<br />

Turns off all indoor<br />

units<br />

The input signal is recognized during its falling phase. (After reaching the bottom of the falling edge, the signal must<br />

remain there for at least 100 ms.)<br />

CAUTION<br />

(1) Do not turn on the COOL (SW1) and HEAT (SW2) terminals simultaneously.<br />

(2) Be sure to provide a contact for each terminal.<br />

External signal: No-voltage pulse contact<br />

The optional P.C. board should be connected to the header outdoor unit (U1).<br />