Check code Check code name<br />

Cause<br />

[E15] / [42]<br />

(AI-NET)<br />

No corresponding indoor unit<br />

during automatic address<br />

1. Communication line connection error between<br />

indoor and outdoor<br />

2. Indoor power system error<br />

3. Noise from surrounding devices<br />

4. Power failure<br />

5. Indoor P.C. board error<br />

Is communication<br />

line between indoor<br />

and outdoor<br />

normal?<br />

Yes<br />

No<br />

Correct communication line.<br />

Is connection of<br />

CN40 connector on<br />

indoor P.C. board<br />

correct?<br />

No<br />

Correct connection of<br />

connector.<br />

Yes<br />

Is<br />

connection of CN01<br />

connector on I/F P.C. board<br />

of header outdoor unit<br />

correct?<br />

No<br />

Correct connection of<br />

connector.<br />

Yes<br />

Is there any connection<br />

error of power wire?<br />

Yes<br />

Correct power wire.<br />

No<br />

Did a power failure<br />

occur?<br />

Yes<br />

Set up address again after<br />

resetting power supply.<br />

No<br />

Is there no noise source?<br />

Yes<br />

Eliminate noise.<br />

No<br />

Set up address again after<br />

resetting power supply.<br />

Check code Check code name<br />

Cause<br />

[E09] / [99]<br />

(AI-NET)<br />

Duplicated header remote<br />

controller<br />

Setup of header remote controller is duplicated.<br />

Are two remote<br />

controllers set up as two<br />

header remote<br />

controllers?<br />

Yes<br />

Set up one controller as the header and<br />

the other follower.<br />

(Remote controller address connector)<br />

No<br />

Check remote controller P.C. board.<br />

Failure ➝ Replace<br />

Check code Check code name<br />

Cause<br />

[E10] / [CF]<br />

(AI-NET)<br />

Communication error between<br />

indoor MCUs.<br />

Indoor P.C. board error.<br />

Is there any trouble on<br />

power line?<br />

Yes<br />

Check power voltage. Improve the<br />

line condition. Eliminate noise, etc.<br />

No<br />

Check indoor control P.C. board.<br />

Failure ➝ Replace<br />

Check code Check code name<br />

Cause<br />

[E12] / [42]<br />

(AI-NET)<br />

Automatic address start error<br />

1. Starting automatic addressing of indoor units during<br />

automatic addressing in another refrigerant line.<br />

(Sub-code: 01)<br />

2. Starting automatic addressing of outdoor units<br />

during automatic addressing of indoor units<br />

(Sub-code: 02)<br />

Sub-code: 01: Communication between indoor and outdoor 02: Communication between outdoor units<br />

Are U1, U2, U3, and<br />

U4 connectors<br />

connected?<br />

No<br />

Yes<br />

Disconnect connector connection<br />

of U1, U2, U3, and U4.<br />

Turn on power of outdoor unit<br />

again.<br />

Set up address again.<br />

(Refer to “7-4-3. Address Setup<br />

Procedure”.)<br />

197