High-pressure sensor<br />

(SV3D)<br />

SV<br />

Oil<br />

separator<br />

(SV41)<br />

SV<br />

Highpressure<br />

(SV3C)<br />

(TD1)<br />

SW<br />

(TK4)<br />

TK5)<br />

SV3E)<br />

Distributor<br />

SV<br />

SV<br />

(SV2)<br />

SV (SV42) SV<br />

Highpressure<br />

SW<br />

Highpressure<br />

(TD2)<br />

SW<br />

(SV43)<br />

(TD3)<br />

(TK2)<br />

(TK3)<br />

Oil header<br />

SV<br />

(SV3F)<br />

(3)<br />

SV<br />

(SV3B)<br />

(8)<br />

(4)<br />

SV<br />

SV<br />

SV<br />

Check code Check code name<br />

Cause<br />

[H08] / [d4]<br />

(AI-NET)<br />

Oil level detective temperature<br />

sensor error<br />

TK1 to TK5 sensor Open/Short<br />

Sub-code:<br />

01: TK1 sensor error 02: TK2 sensor error 03: TK3 sensor error<br />

04: TK4 sensor error 05: TK5 sensor error<br />

The detected error is an oil level detective temperature sensor error. Check disconnection of the wiring and resistance<br />

value of the sensor.<br />

If the sensors are normal, replace the outdoor I/F P.C. board.<br />

Circuit<br />

TK1<br />

TK2<br />

TK3<br />

TK4<br />

TK5<br />

Connector<br />

CN531 (Black)<br />

CN532 (Green)<br />

CN533 (Pink)<br />

CN534 (Yellow)<br />

CN535 (Red)<br />

Check code Check code name<br />

Cause<br />

[H16] / [d7]<br />

(AI-NET)<br />

Oil level detection circuit error<br />

TK1 temperature detective circuit<br />

error<br />

(Sub-code: 01)<br />

1. Coming-off of TK1 sensor, miswiring, characteristics<br />

error of resistance value<br />

2. Oil-equalization circuit error (Check valve, capillary<br />

clogging, strainer clogging)<br />

3. Refrigerant stagnation in the compressor shell<br />

Is not TK1 sensor<br />

detached?<br />

Yes<br />

Correct installation of sensor.<br />

No<br />

Is there<br />

no miswiring or<br />

misinstallation on<br />

TK1/TK2/TK3/TK4/TK5<br />

sensors?<br />

No<br />

Yes<br />

Correct miswiring/misinstallation.<br />

TK1: CN531, black<br />

TK2: CN532, green<br />

TK3: CN533, pink<br />

TK4: CN534, yellow<br />

TK5: CN535, red<br />

Are<br />

characteristics of<br />

TK1 sensor resistance<br />

value normal?<br />

Yes<br />

No<br />

*See “Outdoor unit temperature sensor<br />

characteristics” on “8-9. Sensor Characteristics”.<br />

Sensor error<br />

Start a test operation in COOL or HEAT mode.<br />

↓<br />

Display TK1 sensor temperature on 7-segment display with<br />

SW01/02/03=[1] [12] [2].<br />

↓<br />

Check TK1 sensor temp approx. 10 minutes after compressor 1 has operated.<br />

If low temperature continues (approximately outside temp) or temperature has<br />

little change, a clogging of strainer of oil-equalization circuit, clogging of<br />

capillary tube, or malfunction of check valve is considered.<br />

No error<br />

Error<br />

Compressor<br />

Strainer<br />

Capillary<br />

TK1<br />

Replace clogging part.<br />

Check the<br />

clogging of SV3E<br />

valve. (Note 1)<br />

Error<br />

(Note 1) Refer to the article of the check code [H07].<br />

Replace SV3E valve.<br />

No error<br />

Check I/F P.C. board<br />

MMY-MAP1404∗<br />

MMY-MAP1604∗<br />

Compressor<br />

(Inverter)<br />

Compressor<br />

Compressor<br />

(Inverter)<br />

(Inverter)<br />

1<br />

1<br />

2<br />

3<br />

209