Check code Check code name<br />

Cause<br />

[F23] / [43]<br />

(AI-NET)<br />

Ps sensor error Output voltage error of Ps sensor<br />

Is connection of Ps<br />

sensor connector<br />

correct?<br />

No<br />

Connector: CN500, White<br />

Correct connection of<br />

connector.<br />

Yes<br />

Are output<br />

voltage characteristics<br />

of Ps sensor<br />

normal?<br />

Yes<br />

No<br />

(1) Pressure (Check joint) by pressure gauge<br />

(2) Pressure display on 7-segment display<br />

(3) Output voltage of I/F P.C. board<br />

If (1) and (2), (3) are different, an error of pressure<br />

sensor itself is considered.<br />

If (2) and (3) are different, check interface P.C. board.<br />

Sensor error ➝ Replace<br />

Is there no leakage<br />

from SV4 valve?<br />

Is not<br />

refrigerant bypassed from<br />

No<br />

discharge to suction of<br />

No<br />

4-way valve?<br />

Check compressor.<br />

Yes Yes<br />

Replace SV4 valve. Check 4-way valve.<br />

Check code Check code name<br />

Cause<br />

[F24] / [43] Pd sensor error Output voltage error of Pd sensor<br />

(AI-NET)<br />

It is output voltage error of Pd sensor. Check disconnection of connection of connector (Pd sensor: CN501, red)<br />

circuit and output voltage of sensor.<br />

If the sensor is normal, replace outdoor I/F P.C. board.<br />

Check code Check code name<br />

Cause<br />

[F16] / [43]<br />

(AI-NET)<br />

Outdoor pressure sensor<br />

miswiring (Pd, Ps)<br />

1. High-pressure Pd sensor and low pressure sensor<br />

Ps are exchanged.<br />

2. Output voltage of each sensor is zero.<br />

Are connection of<br />

Pd sensor and Ps<br />

sensor connectors<br />

correct?<br />

No<br />

Correct connection of connectors.<br />

Pd sensor: CN501, Red<br />

Ps sensor: CN500, White<br />

Yes<br />

Are output<br />

voltage characteristics<br />

of Pd sensor and Ps<br />

sensor normal?<br />

Yes<br />

Are Pd/Ps<br />

output values<br />

Pd>Ps during<br />

compressor<br />

operation?<br />

No<br />

(1) Pressure (Check joint) by pressure gauge<br />

(2) Pressure display on 7-segment display<br />

(3) Output voltage of I/F P.C. board<br />

If (1) and (2), (3) are different, an error of pressure<br />

sensor itself is considered.<br />

If (2) and (3) are different, check interface P.C. board.<br />

No<br />

Value can be confirmed by 7-segment<br />

display function on outdoor I/F P.C. board.<br />

Sensor error ➝ Replace<br />

Check compressor.<br />

Yes<br />

Pd SW01/02/03=1/1/2<br />

Ps SW01/02/03=1/2/2<br />

Check outdoor I/F P.C. board.<br />

Defect ➝ Replace<br />

Check code Check code name<br />

Cause<br />

[F22] / [B2] TD3 sensor error TD3 sensor Open/Short<br />

(AI-NET)<br />

This error code means detection of Open/Short of TD3 sensor. Check disconnection of circuit for connection of<br />

connector (TD3 sensor: CN504, blue) and characteristics of sensor resistance value. (See “Outdoor unit temperature<br />

sensor characteristics” on “8-9. Sensor Characteristics”.)<br />

If sensor is normal, replace outdoor I/F P.C. board.<br />