(2) Indoor unit setup method for priority indoor unit mode<br />

The setting can be changed only when the system is at rest. (Be sure to turn<br />

off the system prior to this operation.)<br />

1 Push the + + buttons simultaneously and hold for at<br />

least 4 seconds. The display window will start flashing in a little<br />

while.<br />

Verify that the displayed CODE No. is 10.<br />

• If the displayed CODE No. is not 10, press the button to erase the<br />

display and repeat the procedure from the beginning.<br />

(Note that the system does not respond to remote controller operation<br />

for about 1 minute after the button is pushed.)<br />

(In the case of group control, the indoor unit No. displayed first indicates<br />

the header unit.)<br />

3<br />

TEMP.<br />

FILTER<br />

RESET TEST<br />

TIMER SET<br />

SET<br />

TIME<br />

CL<br />

FAN<br />

SAVE<br />

SWING/FIX<br />

ON / OFF<br />

5 4<br />

6 1 2<br />

MODE<br />

VENT<br />

UNIT LOUVER<br />

2<br />

UNIT LOUVER<br />

Each time the button is pushed, one of the indoor<br />

unit Nos. under group control is displayed in turn. Select<br />

the indoor unit whose setting is to be changed.<br />

The fan and flap of the selected indoor unit then come on, so<br />

that the position of this unit can be confirmed.<br />

3 Use the button to select the CODE No. 04.<br />

4 Use the button to select the SET DATA 0001.<br />

Priority set 0001 No priority set 0000<br />

5 Push the button.<br />

The setup is finished when the display changes from flashing to steady.<br />

6 Upon finishing the setup, push the button. (This<br />

finalizes the setting.)<br />

When the button is pushed, the display goes blank, and the<br />

system returns to normal off state.<br />

(Note that the system does not respond to remote controller<br />

operation for about 1 minute after the button is pushed.)<br />

NOTE<br />

Priority can be given to only one indoor unit. If more than one indoor unit is accidentally set to priority, an error code<br />

(L5 or L6: Duplicated indoor unit priority setting) will be displayed.<br />

All units displaying L5 have been set to 0001 (priority). Keep the unit to which priority should be given as it is, and<br />

change the value back to 0000 (no priority) for all the rest.<br />

Error code<br />

Description<br />

Duplicated indoor unit priority setting (The unit is set to 0001.)<br />

Duplicated indoor unit priority setting (The unit is set to 0000.)<br />

108