7-7-3. Error Clearing Function<br />

(1)Clearing from the main remote controller<br />

▼ Error clearing in outdoor unit<br />

Error of the outdoor unit currently detected is cleared by the unit of one refrigerant circuit system to which the indoor<br />

units operated by the remote controller is connected. (Error of the indoor unit is not cleared.)<br />

For clearing errors, the service monitor function of the remote controller is used.<br />

<br />

1 Change the mode to service monitor mode by pushing + buttons simultaneously for 4<br />

seconds or more.<br />

2 Using buttons, set CODE No. to “FF”.<br />

3 The display in Section A in the following figure is counted with interval of 5 seconds as<br />

“0005” --> “0004” --> “0003” --> “0002” --> “0001” --> “0000”.<br />

When the count arrives “0000”, the error is cleared.<br />

*However, counting from “0005” is repeated on the display.<br />

4 When button is pushed, the status returns to the normal status.<br />

Section A<br />

TEMP.<br />

ON / OFF<br />

2<br />

TIMER SET<br />

FAN<br />

MODE<br />

TIME<br />

SAVE<br />

VENT<br />

FILTER<br />

RESET TEST<br />

SET<br />

CL<br />

SWING/FIX<br />

UNIT LOUVER<br />

4<br />

1 3<br />

▼ Error clearing in indoor unit<br />

Error in the indoor unit is cleared by button on the remote controller.<br />

(Only error of the indoor unit connected with operating remote controller is cleared.)<br />

155