Check code Check code name<br />

Cause<br />

[P19] / [08]<br />

(AI-NET)<br />

4-way valve reverse error 1. 4-way valve error<br />

2. TS1 sensor/TE1 sensor error<br />

3. Pd sensor/Ps sensor error<br />

4. TE sensor/TL sensor misconnection<br />

Sub-code: Detected outdoor unit No.<br />

Is 4-way valve<br />

coil connector<br />

connected?<br />

No<br />

Correct connector connection.<br />

(4-way valve coil: CN317)<br />

Yes<br />

Are output voltage<br />

characteristics of Pd and<br />

Ps sensors normal?<br />

No<br />

Sensor error<br />

Yes<br />

Are<br />

characteristics of<br />

resistance value of TS1,<br />

TE1 and TL sensors<br />

normal?<br />

Yes<br />

No<br />

* See “Outdoor unit temperature sensor<br />

characteristics” on “8-9. Sensor Characteristics”.<br />

Sensor error<br />

Are TS1, TE1<br />

and TL sensor<br />

connectors connected<br />

normally?<br />

No<br />

Correct connector connection<br />

TS1 sensor: CN505<br />

TE1 sensor: CN520<br />

TL sensor: CN523<br />

Reset the power supply and<br />

start heating test operation.<br />

Does 4-way valve<br />

operate?<br />

No<br />

Does<br />

Yes discharge refrigerant No<br />

gas bypass to suction<br />

side through 4-way<br />

valve? *1<br />

Yes<br />

If no error occurs in the test<br />

operation, restart operation.<br />

4-way valve error Check 4-way valve.<br />

*1 Check TS1 and TE1 temperature of the outdoor unit which is running.<br />

(I/F) SW01=[1], SW02=[6], SW03=[2] ➝ TS sensor temperature<br />

SW01=[1], SW02=[7], SW03=[2] ➝ TE sensor temperature<br />

<br />

TE1 sensor: Normal if TE1 is 30°C or less in the seasons except<br />

summer (Outside temp 20°C or lower)<br />

TS1 sensor: Normal if TS is 50°C or less in the seasons except<br />

summer (Outside temp 20°C or lower)<br />

Check code Check code name<br />

Cause<br />

[P18] / [E2]<br />

(AI-NET)<br />

Discharge temp TD3 error 1. Outdoor unit service valve closed<br />

2. Outdoor PMV error<br />

3. TD sensor error<br />

4. Refrigerant shortage, clogging of refrigerant circuit<br />

5. 4-way valve error<br />

6. SV4 circuit leakage, misinstallation<br />

Are service<br />

valves of gas and<br />

liquid sides fully<br />

opened?<br />

No<br />

Open service valves fully.<br />

Yes<br />

Is outdoor PMV normal?<br />

1. Connector connection<br />

2. Wiring<br />

3. Coil<br />

4. Valve body<br />

5. Outdoor I/F P.C. board<br />

No<br />

Connectors: PMV1: CN300,<br />

PMV2: CN301, PMV4: CN303<br />

Repair outdoor PMV.<br />

Yes<br />

Are<br />

characteristics of TD3<br />

sensor resistance<br />

normal?<br />

Yes<br />

No<br />

* See “Outdoor unit temperature sensor<br />

characteristics” on “8-9. Sensor Characteristics”.<br />

Replace TD3 sensor.<br />

Does<br />

discharge refrigerant<br />

gas bypass to suction<br />

side through 4-way<br />

valve?<br />

Yes<br />

Check 4-way valve.<br />

No<br />

SV4 circuit<br />

1. Are SV41, SV42 and SV43<br />

valve coils installed correctly?<br />

2. Is SV42 circuit sealed<br />

correctly (no leakage)?<br />

No<br />

Correct installation of valve<br />

coil.<br />

Replace SV43 valve.<br />

Yes<br />

Are indoor units of a<br />

different refrigerant line<br />

connected?<br />

No<br />

Yes<br />

(Check it using the miswiring check<br />

function of the outdoor unit.)<br />

Correct wiring<br />

Refrigerant shortage,<br />

clogging, pipe breakage<br />

(Check there is no pipe breakage, and<br />

then recharge the refrigerant.)<br />

221