5 Control Outline<br />

Indoor Unit<br />

Control Specifications<br />

NO. Item Specification outline Remarks<br />

1<br />

2<br />

Upon power<br />

supply reset<br />

Operation<br />

selection<br />

1. Identification of outdoor unit<br />

When the power supply is reset, the outdoor unit is identified, and control is<br />

redirected according to the identification result.<br />

2. Indoor fan speed and air flow direction control availability settings<br />

Settings such as indoor fan speed and air flow direction control availability are<br />

replaced on the basis of EEPROM data.<br />

3. If power supply reset is performed in the wake of a fault, the check code is cleared.<br />

If the abnormality persists after the Start/Stop button on the remote controller is<br />

pressed to resume operation, the check code is redisplayed on the remote<br />

controller.<br />

1. The operation mode changes in response to an operation selection command<br />

issued via the remote controller.<br />

Remote controller command<br />

STOP<br />

FAN<br />

COOL<br />

DRY<br />

HEAT<br />

Control outline<br />

Air conditioner shutdown<br />

Fan operation<br />

Cooling operation<br />

Drying operation<br />

Heating operation<br />

Ts: Temperature<br />

setting<br />

Ta: Room temperature<br />

Room temp.<br />

control<br />

1. Adjustment range - remote controller temperature setting (°C)<br />

COOL/DRY HEAT<br />

Wired type 18~29 18~29<br />

Wireless type 18~30 16~30<br />

Shift in heating suction<br />

temperature<br />

(not applicable to<br />

remote controller<br />

thermo operation)<br />

3<br />

2. In heating operation, the temperature setting may be fine-tuned via the DN code<br />

“06”.<br />

SET DATA 0 2 4 6<br />

Temperature setting adjustment +0°C +2°C +4°C +6°C<br />

Factory default<br />

SET DATA<br />

2<br />

4<br />

Automatic<br />

capacity control<br />

1. The outdoor unit determines the operational capacities of indoor units according<br />

to the difference between Ta and Ts.<br />

Ta<br />

(°C)<br />

+2<br />

+1<br />

Ts<br />

-1<br />

Cooling<br />

SD<br />

SB<br />

S9<br />

S7<br />

S5<br />

S3<br />

S0<br />

Ta<br />

(°C)<br />

+1<br />

Ts<br />

-1<br />

-2<br />

Heating<br />

S3<br />

S0<br />

S5<br />

S7<br />

S9<br />

SB<br />

SD<br />

SF<br />

Ts: Temperature<br />

setting<br />

Ta: Room temperature<br />

70