(4) Individual start/stop (ON/OFF) individual test operation function<br />

This function is provided to start/stop (ON/OFF) individually each indoor unit connected to the same system by<br />

using switches on the interface board of the header unit.<br />

Set SW01 [16] and set SW02, SW03 to indoor address No. (1 to 64) to be started (Refer to the following table*) -<br />

only the setup indoor unit starts operation.<br />

(In the rotary switches of the indoor unit which operates in a group by the remote controller, the follower unit cannot<br />

be individually started or stopped. In this case, [ - - ] is displayed on 7-segment display [B] on the interface P.C.<br />

board of the header unit.)<br />

<br />

0<br />

Power ON<br />

Be sure to turn on power at the indoor side<br />

before power-ON of outdoor unit.<br />

If an error is already displayed with SW01/SW02/SW03<br />

being [1/1/1], return the status to normal one according<br />

to troubleshooting and then execute a test operation.<br />

Set up the operation mode of the remote controller.<br />

(If it is not set up, the operation continues with the<br />

current mode.)<br />

The unit which is not given with priority by heating<br />

priority control, cooling priority control, and selection<br />

of cooling or heating mode is not operated.<br />

In this case, " operation ready" or " operation<br />

mode controlled" is displayed on the remote controller.<br />

7-segment display [A]<br />

SW04<br />

7-segment display [B]<br />

SW05<br />

Match the rotary<br />

switches on the<br />

interface P.C.<br />

board of the<br />

header unit to the<br />

following table*.<br />

(7-segment display)<br />

[A]<br />

[ ]<br />

Address display<br />

of corresponding<br />

indoor unit<br />

[B]<br />

[ ]<br />

[ 00] is displayed<br />

for 5 seconds after<br />

operation-ON.<br />

SW01 SW02 SW03<br />

<br />

Press the push-switch SW04 on the same board for 2<br />

seconds or more.<br />

(If pressed continuously for 10 seconds or more, the<br />

operation changes to the individual test operation.)<br />

[A]<br />

[ ]<br />

Address display<br />

of corresponding<br />

indoor unit<br />

(7-segment display)<br />

[B]<br />

[ ]<br />

[ 11] is displayed for 5 seconds after operation-ON.<br />

(For individual test operation, [ FF] is displayed.)<br />

Start<br />

The indoor unit to be started operates.<br />

Operation check<br />

If the discharge temperature does not change<br />

though COOL or HEAT has been set up from the<br />

remote controller, misconnection is considered.<br />

Press the push-switch SW05<br />

on the interface P.C. board of<br />

the header unit for 2 seconds<br />

or more.<br />

(7-segment display)<br />

[A]<br />

[ ]<br />

Address display<br />

of corresponding<br />

indoor unit<br />

After test operation, return the display select switches<br />

SW01/SW02/SW03 on the interface P.C. board of the<br />

header unit to [1/1/1].<br />

[B]<br />

[ ]<br />

[ 00] is displayed<br />

for 5 seconds after<br />

operation-ON.<br />

End<br />

* SW01 SW02 SW03 Units to be operated<br />

16 1~16 1<br />

16 1~16 2<br />

16 1~16 3<br />

16 1~16 4<br />

Address 1 to<br />

Address 16 }<br />

individually<br />

Address 17 to<br />

Address 32 }<br />

individually<br />

Address 33 to<br />

Address 48 }<br />

individually<br />

Address 49 to<br />

Address 64 }<br />

individually<br />

In individual<br />

start/stop<br />

NOTE)<br />

The individual test operation returns to the normal operation after 60 minutes.<br />