Item Description of operation, numerical data, and other information Remarks<br />

8. Release<br />

valve control<br />

(cont’d)<br />

9. High<br />

pressure<br />

release<br />

compressor<br />

shutdown<br />

control<br />

10. Case<br />

heater<br />

control<br />

4. SV41, 42, 43 low pressure release control<br />

This control function is aimed at providing low pressure protection, and is individually<br />

performed by the header unit and each follower unit.<br />

The control takes place during defrost operation, heating startup pattern control<br />

operation, and cooling operation.<br />

1)Control details (heating)<br />

When Ps pressure becomes 0.1 MPa, SV41, 42 and 43 are opened; when Ps<br />

pressure becomes 0.15 MPa, SV41, 42 and 43 are closed.<br />

2)Control details (cooling)<br />

When Ps pressure and Pd pressure become 0.14 MPa and 1.8 MPa,<br />

respectively, SV41 and 42 are opened; when Ps pressure and Pd pressure<br />

become 0.19 MPa and 2.2 MPa, respectively, SV41 and 42 are closed.<br />

5. SV5 high pressure release control<br />

This control function is aimed at mitigating pressure rise and is only performed by the<br />

header unit.<br />

1)Control details (heating)<br />

When Pd pressure and compressor speed become 3.4 MPa and 38 rps,<br />

respectively, during heating, with a single compressor in operation, SV5 is opened;<br />

when Pd pressure becomes 2.7 MPa, or compressor speed 64 rps, SV5 is<br />

closed.<br />

This control function is aimed at automatically shutting down a compressor in an<br />

outdoor unit depending on Pd pressure. It is individually performed by the header unit<br />

and each follower unit.<br />

1)Control details<br />

• Compressors are shut down when Pd pressure reaches or exceeds P0.<br />

• The compressor restart prevention timer (2 minutes 30 seconds) is set, and the control<br />

terminated.<br />

There are two types of case heaters: a compressor case heater and an accumulator<br />

case heater. This control function is aimed at preventing the accumulation of refrigerant<br />

in those cases, and is performed by all outdoor units.<br />

If the power supply has not been turned on for a specified period before a postinstallation<br />

test run, compressor failure may occur. Similarly, when starting<br />

compressors after a long period of no power supply, it is recommended that the power<br />

supply be turned on for a while before operation is resumed, just like a post-installation<br />

test run.<br />

This control function is sometimes used alongside an electrical charging of the<br />

compressor motor windings. In this case, a charging sound may be heard, but this is<br />

normal.<br />

1)Control details<br />

• The heaters are turned on while the compressors are turned off.<br />

• The heaters are turned off when T0 sensor temperature becomes 28 °C, and are<br />

turned back on when T0 sensor temperature becomes 25 °C.<br />

• When the compressors are turned on, the heaters are kept on for 10 minutes.<br />

• When Pd P0 = 3.45 MPa,<br />

compressor No. 2 or No. 3<br />

(the last one of three<br />

compressors in terms of<br />

startup order in a three<br />

compressor configuration) is<br />

shut down.<br />

• When Pd P0 = 3.5 MPa,<br />

compressor No. 1 (the first<br />

compressor in terms of<br />

startup order) is shut down.<br />

82