Main<br />

remote<br />

controller<br />

Check code<br />

Outdoor 7-segment display<br />

Check<br />

code<br />

Sub-code<br />

AI-NET central<br />

control<br />

remote<br />

controller<br />

Location<br />

of<br />

detection<br />

Description<br />

System status<br />

Error detection<br />

condition(s)<br />

Check items (locations)<br />

P19<br />

P19<br />

Detected<br />

outdoor unit<br />

No.<br />

8<br />

I/F<br />

4-way valve<br />

reversing error<br />

All stop<br />

Abnormal refrigerating cycle<br />

data is collected during<br />

heating operation.<br />

• Check for defect in main<br />

body of 4-way valve.<br />

• Check for coil defect in 4-<br />

way valve and loose<br />

connection of its<br />

connector.<br />

• Check resistance<br />

characteristics of TS1 and<br />

TE1 sensors.<br />

• Check output voltage<br />

characteristics of Pd and<br />

Ps pressure sensors.<br />

• Check for wiring error<br />

involving TE1 and TL<br />

sensors.<br />

P20 P20 – 22<br />

I/F<br />

Activation of<br />

high-pressure<br />

protection<br />

All stop<br />

Pd sensor detects pressure<br />

equal to or greater than<br />

3.6MPa.<br />

• Check for defect in Pd<br />

pressure sensor.<br />

• Check service valves (gas<br />

side, liquid side) to confirm<br />

full opening.<br />

• Check for defect in outdoor<br />

fan.<br />

• Check for defect in outdoor<br />

fan motor.<br />

• Check outdoor PMVs<br />

(PMV1, 2, 4) for clogging.<br />

• Check indoor/outdoor heat<br />

exchangers for clogging.<br />

• Check for short-circuiting<br />

of outdoor suction/<br />

discharge air flows.<br />

• Check SV2 circuit for<br />

clogging.<br />

• Check for defect in outdoor<br />

P.C. board (I/F).<br />

• Check for defect in indoor<br />

fan system (possible cause<br />

of air flow reduction).<br />

• Check opening status of<br />

indoor PMV.<br />

• Check indoor-outdoor<br />

communication line for<br />

wiring error.<br />

• Check for faulty operation<br />

of check valve in discharge<br />

pipe convergent section.<br />

• Check gas balancing SV4<br />

valve circuit.<br />

• Check SV5 valve circuit.<br />

• Check for refrigerant<br />

overcharging.<br />