12OUTDOOR UNIT PARTS REPLACEMENT<br />

METHODS<br />

No. Part to be replaced Work procedure Remarks<br />

1 Cabinet<br />

2) Discharge cabinet Screws (4 corners)<br />

WARNING<br />

Wear a pair of gloves.<br />

Otherwise, you will risk an injury involving a<br />

replacement part or some other object.<br />

1. Detachment<br />

1)Stop the air conditioner operation, and turn off the<br />

circuit breaker.<br />

2)Remove the screws for the discharge cabinet.<br />

(M5 × 10, 4 pcs.)<br />

With a 14, 16HP unit, the discharge cabinet<br />

side covers need to be removed.<br />

Left and right: (M5 × 2, 2 pcs.) - 2 sets<br />

3)Remove the screws for the lower cabinet.<br />

Front and rear: (M5 × 10, 7 pcs. for front and 6<br />

pcs. for rear)<br />

4)Remove the screws for the service panel.<br />

(M5 × 10, 2 pcs.)<br />

5)Remove the screws for the suction cabinet.<br />

Front and rear: (M5 × 10, 4 pcs. each)<br />

In the case of a 14, 16HP unit: M5 × 10, 5 pcs.<br />

each<br />

6)Remove the screws for the discharge cabinet side<br />

cabinet.<br />

Left and right: (M5 × 10, 6 pcs. each)<br />

2. Attachment<br />

Carry out installation by following the detachment<br />

procedure in reverse (6) ➝ 1)).<br />

Be careful of the hooks provided on the suction<br />

cabinet, service panel and lower cabinet.<br />

Screws (4 corners)<br />

5) Suction cabinet (front and rear)<br />

4) Service panel 3) Lower cabinet (front and rear)<br />

Hook<br />

Discharge cabinet<br />

side cover<br />

6) Side cabinet<br />

(left and right)<br />

Service panel<br />

263