7-7-4. Remote Controller Distinction Function<br />

This function is provided to distinguish the remote controller connected to the indoor unit from the outdoor unit for<br />

a refrigerant circuit system by using switches on the interface P.C. board of the header unit.<br />

<br />

Power ON<br />

Be sure to turn on the power of the indoor unit<br />

prior to the power of the outdoor unit.<br />

Set the display select switches on the<br />

interface P.C. board of the header unit<br />

as follows:<br />

Set SW01/SW02/SW03 to [2/4/1]<br />

7-segment display<br />

[A] [B]<br />

[ A 1 ] [ ]<br />

Operation<br />

Press the push-switch SW04 on the<br />

same board for 2 seconds or more.<br />

7-segment display<br />

[A] [B]<br />

[ A 1 ] [ FF]<br />

"Checking" display of the connected<br />

remote controller flashes.<br />

Check the connected remote controller<br />

Press the push-switch SW05 on the<br />

interface P.C. board of the header<br />

unit for 2 seconds or more.<br />

End<br />

Other end conditions:<br />

1. 10 minutes has passed<br />

2. SW01, SW02, or SW03 changed to other position.<br />

Interface P.C. board<br />

7-segment display [A]<br />

SW04<br />

7-segment display [B]<br />

SW05<br />

SW01 SW02 SW03<br />

<br />

157