CODE No. list (Example)<br />

CODE No. (DN) Item Setting data Factory-set value<br />

01 Filter sign lighting time Depending on Type<br />

02 Filter pollution leve 0000: standard<br />

03 Central control address 0099: Not determined<br />

06 Heating suction temperature shift 0002: +2°C (Floor standing type: 0)<br />

0d Existence of automatic COOL/HEAT mode 0001: No auto mode cooling/heating * Automatically selection<br />

0F Cooling only 0000: Heat pump<br />

by connected outdoor<br />

unit<br />

10 Type Depending on model type<br />

11 Indoor unit capacity Depending on capacity type<br />

12 System address 0099: Not determined<br />

13 Indoor unit address 0099: Not determined<br />

14 Group address 0099: Not determined<br />

19 Louver type (wind direction adjustment) Depending on Type.<br />

1E<br />

Temperature range of cooling/heating<br />

0003: 3 deg (Ts ± 1.5)<br />

automatic SW control point<br />

28 Power failure automatic recovery 0000: None<br />

32 Sensor SW (Selection of static pressure) 0000: Body sensor<br />

5d High ceiling select 0000: Standard<br />

60 Timer setting (wired remote controller) 0000: Available<br />

F0 Swing mode 0001: Standard<br />

F1 Louver fixing position (Flap No. 1) 0000: Not fixed (4-way type only)<br />

F2 Louver fixing position (Flap No. 2) 0000: Not fixed (4-way type only)<br />

F3 Louver fixing position (Flap No. 3) 0000: Not fixed (4-way type only)<br />

F4 Louver fixing position (Flap No. 4) 0000: Not fixed (4-way type only)<br />

Type<br />

Code No. [10]<br />

Setup data Type Model abb. name<br />

0000 1-way Air Discharge Cassette MMU-APSH<br />

0001 *1, *2 4-way Air Discharge Cassette MMU-AP2H<br />

0002 2-way Air Discharge Cassette MMU-APWH<br />

1-way Air Discharge Cassette MMU-APYH<br />

0003<br />

(Compact type)<br />

0004 Concealed Duct Standard MMD-APBH<br />

0005<br />

Slim Duct<br />

MMD-APSPH<br />

MMD-APSH<br />

0006 Concealed Duct High Static Pressure MMD-APH<br />

0007 Under Ceiling MMC-APH<br />

0008 High Wall MMK-APH<br />

0009 — —<br />

0010 Floor Standing Cabinet MML-APH<br />

0011 Floor Standing Concealed MML-APBH<br />

0012 — —<br />

0013 Floor Standing (Below 6HP) MMF-APH<br />

0014 Compact 4-way Air Discharge Cassette MMU-APMH<br />

0016 Fresh air intake unit (Duct type) MMD-APHFE<br />

Indoor unit capacity<br />

CODE No. [11]<br />

Setup data Model Setup data Model<br />

0000* Invalid 0016 —<br />

0001 007 type 0017 048 type<br />

0002 — 0018 056 type<br />

0003 009 type 0019 —<br />

0004 — 0020 —<br />

0005 012 type 0021 072 type<br />

0006 — 0022 —<br />

0007 015 type 0023 096 type<br />

0008 — 0024 —<br />

0009 018 type 0025 —<br />

0010 — 0026 —<br />

0011 024 type 0027 —<br />

0012 027 type 0028 —<br />

0013 030 type ~ —<br />

0014 — 0034 —<br />

0015 036 type<br />

*1 The initial setup value of EEPROM installed on the service P.C. board<br />

*2 <br />

For the above models, set CODE No. to “ ” and the setting data 0000 (initial) to “0001”.<br />