7-4. Address Setup<br />

This product requires address setup before operation.<br />

Follow this procedure for address setup.<br />

7-4-1. Precautions<br />

(1) Address setup is not performed simply by turning on the power supply.<br />

(2) For indoor units, address setup can be done either by manual address setup or by automatic address setup:<br />

Automatic address setup: Setup from SW15 on the interface PC board of the header unit<br />

Manual address setup: Setup from the wired remote controller. (For details, refer to “7-4-3. Address Setup<br />

Procedure.”)<br />

(3) Automatic setup usually takes about 5 minutes per line. In some cases, however, it may take up to 10 minutes.<br />

(4) It is unnecessary to operate the air conditioner to achieve address setup.<br />

7-4-2. Address Setup and Check Procedure<br />

Procedure Item Operation and check contents<br />

1 Indoor unit power-on Turn on the power of the indoor unit for the refrigerant line for which the address is to be set up.<br />

2<br />

3<br />

4<br />

5<br />

Outdoor unit power-on<br />

7-segment display<br />

check<br />

Address setup start<br />

Display check after<br />

setup<br />

System information<br />

check after setup<br />

Turn on the power of all the outdoor units for the refrigerant line for which the address is to be<br />

set up.<br />

Check that “L08” is displayed on the 7-segment display [B] on the interface PC board of the<br />

header unit in the system where the address is to be set up.<br />

Confirm the items in “7-4-3. Address Setup Procedure,” and then set up the address according<br />

to the operation procedure.<br />

(Be careful to note that the setup operation may differ in group control and central control<br />

systems.)<br />

Note:<br />

The address cannot be set up if switches are not operated.<br />

• After address setup, “U1” “ ” is displayed on the 7-segment display.<br />

• For follower outdoor units, “U2” to “U4” are displayed on the 7-segment display [A].<br />

• If an error code is displayed on the 7-segment display [B], remove the cause of the problem<br />

referring to “8 TROUBLESHOOTING.”<br />

Using the 7-segment display function, check the system information of the scheduled system.<br />

(This check is executed on the interface PC board of the header unit.)<br />

6<br />

Rotary switch setup<br />

System capacity 1 2 3<br />

Number of connected<br />

outdoor units<br />

Number of connected<br />

indoor units<br />

7-segment display<br />

SW01 SW02 SW03 [A] [B]<br />

[Number of<br />

horsepower]<br />

[H P]<br />

1 3 3 [Number of units] [ P]<br />

1 4 3<br />

[Number of<br />

connected units]<br />

After the above checks, return rotary switches SW01, SW02, and SW03 to 1/1/1.<br />

Interface PC board<br />

Push switches<br />

7-segment display<br />

[A]<br />

SW04 SW05 SW15<br />

D600 D601 D602 D603 D604<br />

SW01 SW02 SW03<br />

7-segment display<br />

[B]<br />

Rotary switches<br />

124

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!