Check code Check code name<br />

Cause<br />

[H03] / [17]<br />

(AI-NET)<br />

Current detective circuit system<br />

error<br />

1. Wiring or connector connection error on A3-IPDU<br />

P.C. board<br />

2. A3-IPDU P.C. board error<br />

Sub-code:<br />

01: Compressor 1,<br />

02: Compressor 2,<br />

03: Compressor 3<br />

Wiring or<br />

connector<br />

connection on<br />

IPDU P.C. board<br />

normal?<br />

No<br />

Correct connector connection<br />

or wiring.<br />

Yes<br />

Check IPDU P.C. board.<br />

Check code Check code name<br />

Cause<br />

[H02] / [1d]<br />

(AI-NET)<br />

Compressor error (Lock)<br />

1. Outdoor unit power line error<br />

2. Compressor circuit system error<br />

3. Compressor error<br />

4. Refrigerant stagnation in compressor shell<br />

5. A3-IPDU P.C. board error<br />

6. MG-CTT error<br />

Sub-code:<br />

01: Compressor 1,<br />

02: Compressor 2,<br />

03: Compressor 3<br />

Is power voltage<br />

of outdoor unit<br />

normal? *1<br />

Yes<br />

No<br />

*1: 380-415V ± 10%<br />

Correct power line.<br />

Does voltage drop<br />

occur when other<br />

compressor<br />

starts?<br />

No<br />

Yes<br />

Is wiring<br />

or connector<br />

connection on A3-<br />

IPDU P.C. board<br />

normal?<br />

Yes<br />

No<br />

Correct connector connection<br />

or wiring.<br />

Is MG-CTT normal? *2<br />

No<br />

Exchange MG-CTT<br />

Yes<br />

*2 Check connection wiring<br />

Check operation of MG-CTT<br />

Check the short circuit of MG-CTT<br />

Yes<br />

Abnormal overload? Correct cause of overload.<br />

No<br />

Is there no<br />

refrigerant stagnation<br />

in compressor shell?<br />

Yes<br />

Is case heater output<br />

Yes<br />

normal?<br />

Correct refrigerant stagnation<br />

in compressor shell.<br />

No No<br />

Operation starts. Check case heater.<br />

Is compressor<br />

normal? *3<br />

Yes<br />

Check A3-IPDU P.C. board.<br />

No<br />

*3 Check the following items mainly.<br />

1. Existence of abnormal sound and abnormal<br />

vibration during operation or starting<br />

2. Abnormal overheat of case during operation or<br />

stop time (Never touch with hands.)<br />

3. Current of compressor lead during operation or<br />

starting time (No sudden change of current?)<br />

Compressor error<br />

MG-CTT: Magnet contactor<br />

205