Check code Check code name<br />

Cause<br />

[E23] / [15]<br />

(AI-NET)<br />

Communication signal sending<br />

error between outdoor units<br />

1. Inter-unit wire connection error between outdoor units<br />

2. Communication connector connection error<br />

between outdoor units, I/F P.C. board error<br />

3. End terminal resistance setup error between<br />

outdoor units<br />

Is there no<br />

miswiring or disconnection<br />

on communication line<br />

between outdoor<br />

units?<br />

No<br />

Yes<br />

Correct communication line.<br />

Is connection<br />

of CN03 connector on<br />

outdoor I/F P.C. board<br />

normal?<br />

No<br />

Correct wiring or connector.<br />

Yes<br />

Is not main power of<br />

outdoor unit turned<br />

off?<br />

Yes<br />

Turn on main power of<br />

outdoor unit.<br />

No<br />

Is the end<br />

terminal resistance between<br />

outdoor units turned on?<br />

(SW30 Bit 1)<br />

No<br />

Turn the end terminal<br />

resistance to ON.<br />

Yes<br />

Did power failure<br />

occur?<br />

Yes<br />

Clear check code.<br />

No<br />

Is there no noise<br />

source, etc?<br />

Yes<br />

Check and eliminate noise,<br />

etc<br />

No<br />

Check outdoor I/F P.C. board.<br />

Defect ➝ Replace<br />

Check code Check code name<br />

Cause<br />

[E19] / [96]<br />

(AI-NET)<br />

Header outdoor unit quantity error 1. Misconnection of inter-unit wire between indoor and<br />

outdoor<br />

2. Outdoor I/F P.C. board error<br />

Sub-code: 00: No header unit 02: Two or more header units<br />

Are not<br />

communication lines<br />

(U1, U2) between indoor<br />

and outdoor connected<br />

to multiple outdoor<br />

units?<br />

Yes<br />

Connect communication line<br />

between indoor and outdoor<br />

to one unit per 1 system.<br />

No<br />

Is<br />

communication<br />

line between indoor and<br />

outdoor connected to<br />

one unit per 1<br />

system?<br />

No<br />

Connect communication line<br />

between indoor and outdoor.<br />

Yes<br />

Check I/F board.<br />

Reference)<br />

The outdoor unit connected with communication wires (U1, U2) between<br />

indoor and outdoor is automatically recognized as the header unit.<br />

Check code Check code name<br />

Cause<br />

[E20] / [42]<br />

(AI-NET)<br />

Unit connected to other line<br />

during automatic address<br />

When starting automatic indoor address, a device in<br />

another line is connected.<br />

Sub-code: 01: Connection of an outdoor unit in another line 02: Connection of an indoor unit in another line<br />

Separate the connection between the lines following the address setup method.<br />