Check code Check code name Cause<br />

Check code Check code name<br />

Cause<br />

[E08] / [96]<br />

(AI-NET)<br />

Duplicated indoor addresses Indoor addresses are duplicated.<br />

[E07] / [–]<br />

1. Indoor/outdoor communication end terminal<br />

(AI-NET)<br />

Indoor/Outdoor communication<br />

circuit error<br />

(Detected at outdoor side)<br />

resistance setup error<br />

2. Indoor/outdoor communication connection error<br />

Sub-code: Duplicated indoor address<br />

Using a wired remote controller (RBC-AMT32E), check the setup CODE No.<br />

(DN code) 12, 13, and 14.<br />

When there is no address duplication, check to the following flowchart.<br />

Is setup of end<br />

terminal resistance of<br />

outdoor unit normal?<br />

No<br />

Correct setup of end terminal<br />

resistance.<br />

Yes<br />

Is wire connection to<br />

communication line<br />

normal?<br />

Yes<br />

No<br />

Correct wire connection.<br />

Is inter-unit wire<br />

(U1, U2) between indoor<br />

and outdoor shortcircuited?<br />

No<br />

Yes<br />

Correct short-circuit.<br />

Is not communication<br />

line connected to the<br />

different outdoor<br />

unit?<br />

No<br />

Yes<br />

Correct communication line.<br />

Is connection of<br />

inter-unit wire between<br />

indoor and outdoor<br />

correct?<br />

No<br />

Correct communication line.<br />

Is indoor unit quantity<br />

connected to outdoor<br />

unit correct?<br />

Yes<br />

No<br />

Yes<br />

Is there no error on<br />

power wire to outdoor<br />

unit?<br />

Yes<br />

Correct power wire.<br />

No<br />

Set up indoor address again.<br />

Is there noise source? Yes<br />

Is F400 (fuse) on I/F P.C.<br />

board opened?<br />

No<br />

Turn on power to start operation.<br />

No<br />

Yes<br />

* Check conduction with tester.<br />

I/F P.C. board failure<br />

However an emergent operation is<br />

available by inserting connector to<br />

be connected to CN01 to CN33.<br />

Eliminate noise.<br />

Outdoor I/F P.C. board failure<br />

➝ Replace<br />

196