6-8-6. Operation Mode Selection Control<br />

Header outdoor unit<br />

Outdoor unit<br />

interface PCB<br />

CN510<br />

Connection<br />

cable<br />

SW1: Cooling mode specified input switch<br />

SW2: Heating mode specified input switch<br />

Optional PCB<br />

PJ17<br />

COM<br />

COOL<br />

HEAT<br />

TB1<br />

Locally procured<br />

Shield<br />

wire<br />

SW1<br />

SW2<br />

NOTE<br />

SW1: COOL mode selection switch<br />

SW2: HEAT mode selection switch<br />

COOL (SW1)<br />

ON<br />

Input signal<br />

HEAT (SW2)<br />

OFF<br />

Operation<br />

Only cooling<br />

operation allowed<br />

OFF<br />

ON<br />

Only heating<br />

operation allowed<br />

OFF OFF Normal operation<br />

Remarks<br />

*<br />

*<br />

* The display “ (Operation mode selection control in progress)” appears on the remote controller<br />

Indoor unit operation intervention function [only supported by SMMS-i (4 series)]<br />

The statuses of indoor units operating in a mode different from the selected operation mode can be changed by<br />

changing the status of a jumper wire (J01) provided on the interface P.C. board of the header outdoor unit.<br />

Jumper wire<br />

J01 connected<br />

(factory default)<br />

J01 cut<br />

Description of intervention<br />

All indoor units operating in a mode different from the selected operation mode (prohibited-mode indoor units)<br />

become non-priority units (thermostat OFF).<br />

Prohibited-mode indoor units<br />

Operation mode<br />

Operation status<br />

Remote controller<br />

display<br />

COOL Fan operation at air flow rate set via remote controller “ ” operation ready<br />

HEAT Fan operation at extremely low air flow rate<br />

FAN<br />

Fan operation at air flow rate set via remote controller as<br />

normal<br />

The selected operation mode is imposed on all indoor units operating in a different mode.<br />

Mode selected at P.C. board<br />

Remote controller operation / display<br />

Normal<br />

All modes (COOL, DRY, HEAT and<br />

FAN) available<br />

COOL Only COOL, DRY and FAN available “ operation mode control”<br />

HEAT<br />

Only HEAT and FAN available<br />

(turned on during remote<br />

controller operation)<br />

The optional P.C. board should be connected to the header outdoor unit (U1).<br />