6-7. Applied control for Outdoor Unit<br />

The outdoor fan high static pressure support and priority operation mode setting (cooling / heating / number of units<br />

/ or priority indoor unit) functions are made available by setting relevant switches provided on the interface P.C.<br />

board of the outdoor unit.<br />

6-7-1. Outdoor Fan High Static Pressure Shift<br />

Purpose/characteristics<br />

This function is used when connecting a duct to the discharge port of an outdoor unit (as part of, for example, unit<br />

installation on the floor by floor installation.)<br />

Setup<br />

Turn ON the DIP switch [SW10, Bit 2] provided on the interface P.C. board of the outdoor unit.<br />

This function must be enabled with every discharge duct connected outdoor unit for both of the header and follower<br />

units.<br />

Specification<br />

Increase the speed of the propeller fan units on the outdoor fan to allow the installation of a duct with a maximum<br />

external static pressure not greater than specified in the table below. If a discharge duct with a resistance greater<br />

than 15 Pa (1.5 mmAq) is to be used, enable this function. The maximum external static pressures of base units<br />

are shown below (Table 1). In the case of combined use of multiple outdoor units, set all the units to the same<br />

maximum external static pressure as the one with the lowest maximum external static pressure (see table2).<br />

Table 1: Maximum External Static Pressures of Base Outdoor Units<br />

Model MMY- MAP0804 MAP1004 MAP1204 MAP1404 MAP1604<br />

Maximum external static pressure (Pa) 60 60 50 40 40<br />

(*) Outdoor unit air flow (m3/h) 9900 10500 11600 12000 13000<br />

(*) Calculate duct resistance from outdoor unit air flow.<br />

Table 2: Maximum External Static Pressures for Combined Use of Base Units<br />

(1) Standard models<br />

Combined<br />

horsepower output<br />

Model<br />

MMY-<br />

Combination of outdoor units<br />

106<br />

Maximum external<br />

static pressure<br />

(Pa)<br />

Unit 1 Unit 2 Unit 3 Unit 4<br />

8 MAP0804 MAP0804 60<br />

10 MAP1004 MAP1004 60<br />

12 MAP1204 MAP1204 50<br />

14 MAP1404 MAP1404 40<br />

16 AP1614 MAP0804 MAP0804 60<br />

18 AP1814 MAP1004 MAP0804 60<br />

20 AP2014 MAP1004 MAP1004 60<br />

22 AP2214 MAP1204 MAP1004 50<br />

24 AP2414 MAP0804 MAP0804 MAP0804 60<br />

26 AP2614 MAP1004 MAP0804 MAP0804 60<br />

28 AP2814 MAP1004 MAP1004 MAP0804 60<br />

30 AP3014 MAP1004 MAP1004 MAP1004 60<br />

32 AP3214 MAP0804 MAP0804 MAP0804 MAP0804 60<br />

34 AP3414 MAP1004 MAP0804 MAP0804 MAP0804 60<br />

36 AP3614 MAP1004 MAP1004 MAP0804 MAP0804 60<br />

38 AP3814 MAP1004 MAP1004 MAP1004 MAP0804 60<br />

40 AP4014 MAP1004 MAP1004 MAP1004 MAP1004 60<br />

42 AP4214 MAP1204 MAP1004 MAP1004 MAP1004 50<br />

44 AP4414 MAP1204 MAP1204 MAP1004 MAP1004 50<br />

46 AP4614 MAP1204 MAP1204 MAP1204 MAP1004 50<br />

48 AP4814 MAP1204 MAP1204 MAP1204 MAP1204 50