NO. Item Specification outline Remarks<br />

8<br />

9<br />

10<br />

11<br />

12<br />

13<br />

Cooling oil<br />

(refrigerant)<br />

recovery control<br />

Heating<br />

refrigerant (oil)<br />

recovery control<br />

Defrosting<br />

control<br />

Short<br />

intermittent<br />

operation<br />

compensation<br />

control<br />

Drain pump<br />

control<br />

Elimination of<br />

residual heat<br />

While the outdoor unit is recovering cooling oil (refrigerant), the indoor units perform<br />

the following control tasks:<br />

[common for operational (cooling thermo ON / thermo OFF / FAN), as well as nonoperational<br />

indoor units]<br />

1)Open the indoor PMV to a certain degree.<br />

2)Engage in recovery control for a specified period of time and return to normal<br />

cooling operation at the end of this period upon terminating the control.<br />

3)Operate the drain pump throughout the recovery control period and for about 1<br />

minute after it.<br />

While the outdoor unit is recovering heating refrigerant (oil), the indoor units perform<br />

the following control tasks:<br />

1)Open the indoor PMV to a certain degree.<br />

2)Control the indoor fan according to the operation mode.<br />

[Indoor units operating in heating thermo ON/OFF state]<br />

Let the indoor fan continue operating, but turn it off if the temperature of the indoor<br />

heat exchanger drops.<br />

[Indoor units operating in FAN mode]<br />

Turn off the indoor fan and display “HEATING STANDBY ” on the remote<br />

controller.<br />

[Non-operational indoor units]<br />

Keep the indoor fan turned off.<br />

3)Terminate the recovery operation depending on the TC2 temperature reading.<br />

The timing of termination is determined by each indoor unit.<br />

4)Operate the indoor fan and drain pump for about 1 minute after the termination<br />

of the recovery operation. (Applicable to 4-way air discharge cassette type, 2-<br />

way air discharge cassette type and 1-way air discharge cassette type)<br />

While the outdoor unit is engaged in defrosting control, the indoor units perform the<br />

following control tasks:<br />

1)Open the indoor PMV to a certain degree.<br />

2)Control the indoor fan according to the operation mode.<br />

[Indoor units operating in heating thermo ON/OFF state]<br />

Let the indoor fan continue operating for a while, but turn it off as the temperature<br />

of the indoor heat exchanger drops.<br />

[Indoor units operating in FAN mode]<br />

Let the indoor fan continue operating.<br />

[Non-operational indoor units]<br />

Keep the indoor fan turned off.<br />

3)As defrosting control comes to an end, it gives way to heating refrigerant (oil)<br />

recovery control.<br />

(For control details, see “9. Heating refrigerant (oil) recovery control” above.)<br />

1. For 5 minutes after startup, the system is forced to continue operating even if it<br />

reaches the thermo OFF region.<br />

2. However, priority is given to cooling/heating selection, operation standby, and<br />

protective control, so that there is no overriding of thermo OFF in these cases.<br />

• Recovery operation<br />

normally takes place<br />

roughly every 2 hours.<br />

• The opening position<br />

of the indoor PMV<br />

depending on the type<br />

and capacity of the<br />

indoor unit.<br />

• Recovery operation<br />

normally takes place<br />

roughly every hour.<br />

• The opening position<br />

of the indoor PMV<br />

depending on the type<br />

and capacity of the<br />

indoor unit.<br />

• For defrosting<br />

commencement<br />

conditions, see “ 7.<br />

Defrosting control<br />

(reverse defrosting<br />

method)” above.<br />

• The opening position<br />

of the indoor PMV<br />

depending on the type<br />

and capacity of the<br />

indoor unit.<br />

1. During cooling (including DRY operation), the drain pump is operated at all times. Check code [P10]<br />

2. If the float switch is activated while the drain pump is in operation, the drain pump<br />

continues operating, with the relevant check code displayed.<br />

3. If the float switch is activated while the drain pump is turned off, thermo OFF is<br />

forced on the air conditioner, with the drain pump put into operation. If the float<br />

switch continues to be activated for about 5 minutes, the drain pump is turned off,<br />

with the relevant check code displayed.<br />

1. When the air conditioner is turned off after engaging in heating operation, the<br />

indoor fan is operated for about 30 seconds in “breeze” mode.<br />

73