Check code<br />

Display of receiving unit<br />

Outdoor 7-segment display<br />

Sub-code<br />

TCC-LINK<br />

central control<br />

or main remote<br />

controller<br />

display<br />

Indicator light block<br />

Operation Timer Ready<br />

Flash<br />

Typical fault site<br />

Description of error<br />

A3-IPDU Fan A3-IPDU Fan<br />

1 2 3 IPDU 1 2 3 IPDU<br />

01 O<br />

0A O O<br />

02 O 0B O O O<br />

03 O O 0C O O<br />

L29 04 O 0D O O O L29 SIM Error in number of IPDUs<br />

05 O O 0E O O O<br />

06 O O 0F O O O O<br />

07 O O O Circle (O):<br />

08 O Faulty IPDU<br />

09 O O<br />

There are insufficient number of IPDUs (P.C.<br />

boards) in inverter box.<br />

L30 Detected indoor unit No. (L30) SIM<br />

Indoor external error input<br />

(interlock)<br />

P03 – P03<br />

Outdoor discharge (TD1)<br />

ALT<br />

temperature error<br />

00: Open phase detected<br />

Open phase/power failure<br />

P05 01: Compressor 1<br />

P05<br />

ALT Inverter DC voltage (Vdc)<br />

02: Compressor 2<br />

error<br />

03: Compressor 3<br />

MG-CTT error<br />

P07<br />

01: Compressor 1<br />

02: Compressor 2<br />

03: Compressor 3<br />

P07<br />

ALT<br />

Heat sink overheating<br />

error<br />

P10 Indoor unit No. detected (P10) ALT Indoor unit overflow<br />

P13 – P13 ALT<br />

P15<br />

01: TS condition<br />

02: TD condition<br />

P17 – P17 ALT<br />

P18 – P18 ALT<br />

P19 Outdoor unit No. detected P19 ALT<br />

P20 – P20 ALT<br />

P15<br />

Outdoor liquid backflow<br />

detection error<br />

ALT Gas leak detection<br />

Outdoor discharge (TD2)<br />

temperature error<br />

Outdoor discharge (TD3)<br />

temperature error<br />

4-way valve reversing<br />

error<br />

Activation of high-pressure<br />

protection<br />

Indoor unit has been shut down for external error<br />

input in one refrigerant line (detected by indoor<br />

unit).<br />

Outdoor discharge temperature sensor (TD1) has<br />

detected abnormally high temperature.<br />

Open phase is detected when power is turned on.<br />

Inverter DC voltage is too high (overvoltage) or too<br />

low (undervoltage).<br />

Temperature sensor built into IGBT (TH) detects<br />

overheating.<br />

Indoor unit has been shutdown in one refrigerant<br />

line due to detection of overflow (detected by<br />

indoor unit).<br />

State of refrigerant cycle circuit indicates liquid<br />

backflow operation.<br />

Outdoor suction temperature sensor (TS1) detects<br />

sustained and repeated high temperatures that<br />

exceed standard value.<br />

Outdoor discharge temperature sensor (TD2)<br />

detects abnormally high temperature.<br />

Outdoor discharge temperature sensor (TD3)<br />

detects abnormally high temperature.<br />

Abnormality in refrigerating cycle is detected<br />

during heating operation.<br />

High pressure (Pd) sensor detects high pressure<br />

that exceeds standard value.<br />

MG-CTT: Magnet contactor<br />

171