Check code Check code name<br />

Cause<br />

[F15] / [18]<br />

(AI-NET)<br />

Outdoor temp sensor miswiring<br />

(TE1, TL)<br />

1. Misinstallation and misconnection of TE1 sensor<br />

and TL sensor<br />

2. Resistance characteristics error of TE1 sensor and<br />

TL sensor<br />

3. Outdoor P.C. board (I/F) error<br />

Are installed positions<br />

of TE1 sensor and TL<br />

sensor correct?<br />

No<br />

Correct installed positions of<br />

TE1 sensor and TL sensor.<br />

Yes<br />

Outdoor I/F P.C. board<br />

TE1 sensor : CN520, Green<br />

TL sensor : CN523, White<br />

Are connection<br />

of TE1 sensor connector<br />

and TL sensor connector<br />

normal?<br />

No<br />

Correct connection of<br />

connectors.<br />

Yes<br />

Are resistance<br />

characteristics of TL<br />

sensor and TE1 sensor<br />

normal?<br />

No<br />

Correct connection of<br />

connectors.<br />

Yes<br />

* See “Outdoor unit temperature sensor characteristics” on “8-9. Sensor Characteristics”.<br />

Check outdoor I/F P.C. board.<br />

Defect ➝ Replace<br />

TE1 sensor: Outdoor heat exchanger temp sensor<br />

TL sensor: Temp sensor between liquid tanks of outdoor PMV1/2<br />

Check code Check code name<br />

Cause<br />

[F07] / [18]<br />

(AI-NET)<br />

TL sensor error<br />

TL sensor Open/Short<br />

This error code means detection of Open/Short of TL sensor. Check disconnection of circuit for connection of<br />

connector (TL sensor: CN523, White) and characteristics of sensor resistance value. (See “Outdoor unit temperature<br />

sensor characteristics” on “8-9. Sensor Characteristics”.)<br />

If sensor is normal, replace outdoor I/F P.C. board.<br />

Check code Check code name<br />

Cause<br />

[F08] / [1b] TO sensor error TO sensor Open/Short<br />

(AI-NET)<br />

This error code means detection of Open/Short of TO sensor. Check disconnection of circuit for connection of<br />

connector (TO sensor: CN507, Yellow) and characteristics of sensor resistance value. (See “Outdoor unit temperature<br />

sensor characteristics” on “8-9. Sensor Characteristics”.)<br />

If sensor is normal, replace outdoor I/F P.C. board.<br />

Check code Check code name<br />

Cause<br />

[F10] / [0C] Indoor TA sensor error TA sensor Open/Short<br />

(AI-NET)<br />

This error code means detection of Open/Short of TA sensor. Check disconnection of circuit for connection of<br />

connector (TA sensor: CN104, Yellow) and characteristics of sensor resistance value. (See “Indoor unit temperature<br />

sensor characteristics” on “8-9. Sensor Characteristics”.)<br />

If sensor is normal, replace indoor P.C. board.<br />

Check code Check code name<br />

Cause<br />

[F12] / [A2] TS1 sensor error TS1 sensor Open/Short<br />

(AI-NET)<br />

This error code means detection of Open/Short of TS1 sensor. Check disconnection of circuit for connection of<br />

connector (TS1 sensor: CN505, White) and characteristics of sensor resistance value. (See “Outdoor unit temperature<br />

sensor characteristics” on “8-9. Sensor Characteristics”.)<br />

If sensor is normal, replace outdoor I/F P.C. board.<br />

Check code Check code name<br />

Cause<br />

[F13] / [43] TH sensor error IGBT built-in sensor error in A3-IPDU<br />

(AI-NET)<br />

Sub-code: 01: Compressor 1, 02: Compressor 2, 03: Compressor 3<br />

This error code means IGBT built-in temperature sensor error.<br />

Check connection of connectors CN06 on IPDU P.C. board and CN600 on I/F P.C. board.<br />

If sensor is normal, replace IPDU P.C. board.<br />