7-7. Service Support Function<br />

7-7-1. Check Function for Connecting of Refrigerant and Control<br />

Lines<br />

This function is provided to check misconnection of the refrigerant pipes and the control transmission line (Wiring<br />

over lines) between indoor unit and outdoor unit by using the switch on the interface P.C. board of the header unit.<br />

However, be sure to check the following items prior to executing this check function.<br />

1 This check function does not work when a group operation by remote controller is performed and<br />

it is used over outdoor units.<br />

2 When using this check system, be sure to check for each 1 line in the unit of outdoor unit. If<br />

checking the multiple lines at the same time, misjudgment may be caused.<br />

(Check procedure)<br />

Power ON<br />

Be sure to turn on the power at indoor<br />

side before power-ON of outdoor unit.<br />

System capacity check<br />

Set the rotary switches SW01/SW02/SW03 on the interface<br />

P.C. board of the header unit to [1/2/3]. Then the system<br />

capacity is displayed on 7-segment display [A]. Check that<br />

this display surely matches with the expected system<br />

capacity.<br />

(7-segment display)<br />

[A] [B]<br />

[ .] [ HP]<br />

System horsepower<br />

Check No. of outdoor units<br />

Set the rotary switches SW01/SW02/SW03 on the interface<br />

P.C. board of the header unit to [1/3/3]. Then No. of outdoor<br />

units connected to the system is displayed on 7-segment<br />

display [A]. Check that this display surely matches with the<br />

expected No. of outdoor units.<br />

(7-segment display)<br />

[A] [B]<br />

[ .] [ P]<br />

No. of<br />

connected<br />

outdoor units<br />

Check No. of indoor units/No. of units with cooling thermo<br />

ON<br />

Set the rotary switches SW01/SW02/SW03 on the interface<br />

P.C. board of the header unit to [1/4/3]. Then No. of indoor<br />

units connected to the system is displayed on 7-segment<br />

display [A]. Check that this display surely matches with the<br />

expected No. of indoor units.<br />

(7-segment display)<br />

[A] [B]<br />

[ .] [C ]<br />

No. of<br />

connected<br />

outdoor<br />

units<br />

No. of units<br />

with cooling<br />

thermo ON<br />

Check No. of indoor units/No. of units with heating thermo<br />

ON<br />

Set the rotary switches SW01/SW02/SW03 on the interface<br />

P.C. board of the header unit to [1/5/3]. Then No. of indoor<br />

units connected to the system is displayed on 7-segment<br />

display [A]. Check that this display surely matches with the<br />

expected No. of indoor units.<br />

(7-segment display)<br />

[A] [B]<br />

[ .] [H ]<br />

No. of<br />

connected<br />

outdoor<br />

units<br />

No. of units<br />

with heating<br />

thermo ON<br />

Check incorrect wiring<br />

According to the indoor temperature, select one of the<br />

following items for setup of the rotary switches on the<br />

interface P.C. board of the header unit.<br />

Cooling: SW01/SW02/SW03 to [2/1/1]<br />

Heating: SW01/SW02/SW03 to [2/2/1]<br />

(7-segment display)<br />

[A] [B]<br />

Cooling [ J .C ] [ ]<br />

Heating [ J .H ] [ ]<br />

Indoor temperature [°C]<br />

32<br />

18<br />

-10<br />

SW02 to<br />

[2]<br />

(Heating)<br />

SW02 to<br />

[1]<br />

(Cooling)<br />

10 43<br />

Outdoor temperature [°C]<br />

A<br />

148